2023-05-01 09:56:54 | SFR ADDITION |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) PRODUCT APPROVAL (20-1119.13) FOR THE SINGLE HUNG |
| WINDOW IS APPROVED FOR SMALL MISSILE ONLY - A SHUTTER |
| IS REQUIRED FOR THIS WINDOW - PLEASE PROVIDE THE |
| REQUIRED SHUTTER PRODUCT APPROVAL. SMALL MISSILE IS OK |
| FOR WINDOWS ABOVE 30 FEET IN HEIGHT - BELOW 30 FEET |
| LARGE MISSILE TESTED WINDOWS ARE REQUIRED IF NOT USING |
| A SHUTTER. |
| |
| 2) WINDOW MARKED NUMBER 3 ON THE BUILDING ELEVATION |
| VIEW IS NOT ON THE WINDOW SCHEDULE - PLEASE ADD TO THE |
| WINDOW SCHEDULE. |
| |
| 3) PLEASE PROVIDE A PRODUCT APPROVAL FOR THE ROOFING |
| SYSTEM. |
| |
| 4) DRAWING S-1 SHOWS THE BUILDING RISK CATEGORY I - |
| SHOULD BE RISK CATEGORY II PER FBC WPB SECTION 120 |
| |
| 5) DRAWING A-3 GENERAL NOTES SHOW CODE VERSION 2017 - |
| SHOULD BE FBC 2020 |
| |
| 6) PLEASE SHOW THE TERMITE PROTECTION TO BE USED - FBC |
| R318.1 |
| |
| 7) PLEASE PROVIDE A SURVEY. |
| |
| 8) SITE PLAN NEEDS TO SHOW THE LOT DRAINAGE (LOT CANNOT |
| DRAIN TO THE NEIGHBORS PROPERTY) - FBC WPB 107.2.5 SITE |
| PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED WITH THE |
| APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY A SITE |
| PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF NEW |
| CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES |
| AND THE PROPOSED FINISHED GRADES, DEPICTING THE |
| PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD |
| AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT |
| SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| INCLUDED ON A BOUNDARY LINE SURVEY. (PLEASE PROVIDE CUT |
| SECTIONS FOR ANY PROPOSED WATER RETAINING SWALES) |
| |
| |
| |