Plan Review Notes
Plan Review Notes For Permit 22030741
Permit Number 22030741
Review Stop B
Sequence Number 2
Notes
Date Text
2023-05-01 09:56:54SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PRODUCT APPROVAL (20-1119.13) FOR THE SINGLE HUNG
 WINDOW IS APPROVED FOR SMALL MISSILE ONLY - A SHUTTER
 IS REQUIRED FOR THIS WINDOW - PLEASE PROVIDE THE
 REQUIRED SHUTTER PRODUCT APPROVAL. SMALL MISSILE IS OK
 FOR WINDOWS ABOVE 30 FEET IN HEIGHT - BELOW 30 FEET
 LARGE MISSILE TESTED WINDOWS ARE REQUIRED IF NOT USING
 A SHUTTER.
  
 2) WINDOW MARKED NUMBER 3 ON THE BUILDING ELEVATION
 VIEW IS NOT ON THE WINDOW SCHEDULE - PLEASE ADD TO THE
 WINDOW SCHEDULE.
  
 3) PLEASE PROVIDE A PRODUCT APPROVAL FOR THE ROOFING
 SYSTEM.
  
 4) DRAWING S-1 SHOWS THE BUILDING RISK CATEGORY I -
 SHOULD BE RISK CATEGORY II PER FBC WPB SECTION 120
  
 5) DRAWING A-3 GENERAL NOTES SHOW CODE VERSION 2017 -
 SHOULD BE FBC 2020
  
 6) PLEASE SHOW THE TERMITE PROTECTION TO BE USED - FBC
 R318.1
  
 7) PLEASE PROVIDE A SURVEY.
  
 8) SITE PLAN NEEDS TO SHOW THE LOT DRAINAGE (LOT CANNOT
 DRAIN TO THE NEIGHBORS PROPERTY) - FBC WPB 107.2.5 SITE
 PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED WITH THE
 APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY A SITE
 PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF NEW
 CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY. (PLEASE PROVIDE CUT
 SECTIONS FOR ANY PROPOSED WATER RETAINING SWALES)
  
  
  