Plan Review Notes
Plan Review Notes For Permit 22030741
Permit Number 22030741
Review Stop B
Sequence Number 1
Notes
Date Text
2022-05-25 13:11:05SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS, AND
 ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE BUILDING ADDITION
 DESIGNER OF RECORD FBC WPB 107.3.4
  
 2) PLEASE SHOW THE LOCATION OF THE REQUIRED SMOKE
 DETECTORS THROUGH OUT THE HOUSE PER FBC R314.2.2
 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. R314.3 LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1.IN EACH SLEEPING ROOM.
 2.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
  
 3) DRAWING S-1 AND THE WIND DESIGN CALCULATIONS SHOW
 WIND DESIGN CRITERIA AS WIND SPEED 160 MPH, RISK
 CATEGORY I - SHOULD BE - 170 MPH, RISK CATEGORY II
 USING ASCE 7-16 PER FBC WPB SECTION 120
  
 4) DRAWING A-3 GENERAL NOTES SHOW CODE VERSION 2017 -
 SHOULD BE FBC 2020
  
 5) PLEASE SHOW THE TERMITE PROTECTION TO BE USED - FBC
 R318.1
  
 6) PLEASE PROVIDE A SURVEY.
  
 7) SITE PLAN NEEDS TO SHOW THE LOT DRAINAGE (LOT CANNOT
 DRAIN TO THE NEIGHBORS PROPERTY) - FBC WPB 107.2.5 SITE
 PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED WITH THE
 APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY A SITE
 PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF NEW
 CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY. (PLEASE PROVIDE CUT
 SECTIONS FOR ANY PROPOSED WATER RETAINING SWALES)
  
  
  