2022-05-20 13:00:53ACCORDING TO LS-1 THE CONFERENCE ROOM HAS A DOOR WHICH
 COULD BE CLOSED. THIS SEPARATES IT FROM THE RECEPTION
 AREA. REVISE THE PLANS TO SHOW A COMPLETE OUTDOOR AIR
 CALCULATION SHOWING ALL AREAS ACCORDING TO FMC
 403.3.1.1 AND TABLE 403.3.1.1. IF YOU HAVE QUESTIONS OR
 NEED HELP PLEASE DONT HESITATE TO CALL ME.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  