Plan Review Notes
Plan Review Notes For Permit 22030675
Permit Number 22030675
Review Stop M
Sequence Number 2
Notes
Date Text
2022-04-26 16:49:341ST REVIEW FMC
 PERMIT: 22030675
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2-1: THE NUMBER 1 INSIDE A CIRCLE IS STILL ON
 THE DRAWING BUT THERE ARE NO FOOTNOTES OF ANY KIND
 SPELLING OUT WHEN THIS 1 INSIDE A CIRCLE STANDS FOR.
 THE 1 INSIDE A CIRCLE IS IN A COUPLE OF LOCATIONS ON
 THE DRAWING, ONE IS UNDER THE VAV-10-6 AT THE 2 RETURN
 GRILLES. THE OTHER IS LOCATED UNDER THE VAV-10-7.
 PLEASE EXPLAIN WHAT THIS IS OR REMOVE THEY FROM THE
 DRAWING. FBC 107.2.1
  
 2) THE OUTDOOR AIR CALCULATIONS DOES NOT SHOW THE
 CONFERENCE ROOM OR THE RECEPTION AREA. PLEASE ADD THESE
 TO THE OUTDOOR AIR CALCULATIONS. FMC 403.3.3.1.1 AND
 TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  