Plan Review Notes For Permit 22030675 |
Permit Number |
22030675 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-04-26 16:49:34 | 1ST REVIEW FMC | | PERMIT: 22030675 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M2-1: THE NUMBER 1 INSIDE A CIRCLE IS STILL ON | | THE DRAWING BUT THERE ARE NO FOOTNOTES OF ANY KIND | | SPELLING OUT WHEN THIS 1 INSIDE A CIRCLE STANDS FOR. | | THE 1 INSIDE A CIRCLE IS IN A COUPLE OF LOCATIONS ON | | THE DRAWING, ONE IS UNDER THE VAV-10-6 AT THE 2 RETURN | | GRILLES. THE OTHER IS LOCATED UNDER THE VAV-10-7. | | PLEASE EXPLAIN WHAT THIS IS OR REMOVE THEY FROM THE | | DRAWING. FBC 107.2.1 | | | | 2) THE OUTDOOR AIR CALCULATIONS DOES NOT SHOW THE | | CONFERENCE ROOM OR THE RECEPTION AREA. PLEASE ADD THESE | | TO THE OUTDOOR AIR CALCULATIONS. FMC 403.3.3.1.1 AND | | TABLE 403.3.1.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|