Plan Review Notes
Plan Review Notes For Permit 22030665
Permit Number 22030665
Review Stop Z
Sequence Number 1
Notes
Date Text
2022-08-31 17:17:46INSUFFICIENT
  
 1) PROVIDE A SURVEY, PREPARED BY A FLORIDA LICENSED
 SURVEYOR, THAT SHOWS THE RIGHT-OF-WAY LINE, THE
 SIDEWALK, AND ANY TREES WITHIN THE RIGHT-OF-WAY ALONG
 THE ENTIRE FIBER CONDUIT PATH SO THAT STAFF CAN VERIFY
 THAT THE BORE, OPEN TRENCH AND ANY REQUIRED BORE PIT
 AND HANDHOLES ARE WITHIN THE RIGHT-OF-WAY AND NOT ON
 PRIVATE PROPERTY. THE SURVEY NEEDS TO INCLUDE THE
 BROADWAY RIGHT-OF-WAY SECTIONS SO THAT STAFF CAN VERIFY
 THE WOK IS FULLY WITHIN THE RIGHT-OF-WAY.
  
 2) THE ENGINEERING PLAN APPEARS TO SHOW THE EXCAVATION
 FOR HANDHOLE 03+42 AND BORE PIT 06-02 ON PRIVATE
 PROPERTY, WHICH IS NOT PERMITTED UNLESS THE SURVEY
 REQUIRED IN COMMENT #1 CLEARLY SHOWS A GENERAL UTILITY
 EASEMENT AT THE LOCATION.
  
 3) THE CLOSEST EDGE OF THE EXCAVATION FOR BORE PIT
 19+64 MUST SHOW A DIMENSION OF AT LEAST TEN FEET FROM
 THE TRUNK OF THE ADJACENT TREE WITHIN THE RIGHT-OF-WAY.
 THE TREE MUST BE SHOWN ON THE ENGINEERING PLAN. THE
 BORE MACHINE MAY NOT STAGE ADJACENT TO THE TREE.
  
 4) THE CLOSEST EDGE OF THE EXCAVATION FOR BORE PIT
 06-02 MUST SHOW A DIMENSION OF AT LEAST TEN FEET FROM
 THE TRUNK OF THE ADJACENT TREE WITHIN THE RIGHT-OF-WAY.
 THE TREE MUST BE SHOWN ON THE ENGINEERING PLAN. THE
 BORE MACHINE MAY NOT STAGE ADJACENT TO THE TREE.
  
 5) THE TUBULAR MARKERS ARE NOT PERMITTED. MARKERS MAY
 ONLY BE INSTALLED WITHIN THE HANDHOLES OR OTHERWISE
 BURIED.
  
 6) THE BORE DEPTH IS SUFFICIENT TO AVOID TREE ROOTS.
  
 7) PROVIDE A COPY OF THE FDOT ROW PERMIT APPROVING THE
 WORK WITHIN THE BROADWAY RIGHT-OF-WAY.
  