2022-08-31 17:17:46 | INSUFFICIENT |
| |
| 1) PROVIDE A SURVEY, PREPARED BY A FLORIDA LICENSED |
| SURVEYOR, THAT SHOWS THE RIGHT-OF-WAY LINE, THE |
| SIDEWALK, AND ANY TREES WITHIN THE RIGHT-OF-WAY ALONG |
| THE ENTIRE FIBER CONDUIT PATH SO THAT STAFF CAN VERIFY |
| THAT THE BORE, OPEN TRENCH AND ANY REQUIRED BORE PIT |
| AND HANDHOLES ARE WITHIN THE RIGHT-OF-WAY AND NOT ON |
| PRIVATE PROPERTY. THE SURVEY NEEDS TO INCLUDE THE |
| BROADWAY RIGHT-OF-WAY SECTIONS SO THAT STAFF CAN VERIFY |
| THE WOK IS FULLY WITHIN THE RIGHT-OF-WAY. |
| |
| 2) THE ENGINEERING PLAN APPEARS TO SHOW THE EXCAVATION |
| FOR HANDHOLE 03+42 AND BORE PIT 06-02 ON PRIVATE |
| PROPERTY, WHICH IS NOT PERMITTED UNLESS THE SURVEY |
| REQUIRED IN COMMENT #1 CLEARLY SHOWS A GENERAL UTILITY |
| EASEMENT AT THE LOCATION. |
| |
| 3) THE CLOSEST EDGE OF THE EXCAVATION FOR BORE PIT |
| 19+64 MUST SHOW A DIMENSION OF AT LEAST TEN FEET FROM |
| THE TRUNK OF THE ADJACENT TREE WITHIN THE RIGHT-OF-WAY. |
| THE TREE MUST BE SHOWN ON THE ENGINEERING PLAN. THE |
| BORE MACHINE MAY NOT STAGE ADJACENT TO THE TREE. |
| |
| 4) THE CLOSEST EDGE OF THE EXCAVATION FOR BORE PIT |
| 06-02 MUST SHOW A DIMENSION OF AT LEAST TEN FEET FROM |
| THE TRUNK OF THE ADJACENT TREE WITHIN THE RIGHT-OF-WAY. |
| THE TREE MUST BE SHOWN ON THE ENGINEERING PLAN. THE |
| BORE MACHINE MAY NOT STAGE ADJACENT TO THE TREE. |
| |
| 5) THE TUBULAR MARKERS ARE NOT PERMITTED. MARKERS MAY |
| ONLY BE INSTALLED WITHIN THE HANDHOLES OR OTHERWISE |
| BURIED. |
| |
| 6) THE BORE DEPTH IS SUFFICIENT TO AVOID TREE ROOTS. |
| |
| 7) PROVIDE A COPY OF THE FDOT ROW PERMIT APPROVING THE |
| WORK WITHIN THE BROADWAY RIGHT-OF-WAY. |
| |