2022-04-13 16:19:57 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE ARE INDICATIONS OF PROVIDING FOR 2-WAY |
| COMMUNICATIONS IN "AREAS OF REFUGE". |
| |
| AREAS OF REFUGE DOES NOT AAPPEAR TO BE REQUIRED WITHIN |
| THIS OCCUPANCY DUE TO THE INSTALLATION OF A FIRE |
| SPRINKLER SYSTEM. |
| |
| THE FLORIDA BUILDING CODE HAS AN EXEMPTION DUE TO FIRE |
| SPRINKLER INSTALLTION AND OTHER FEATURES OF THE EIT |
| ACCESS. |
| |
| THE FLORIDA LIFE SAFETY CODE REFERENCES AREAS OF REFUGE |
| FOR ACCESSIBLE MEANS OF EGRESS. ACCESSIBLE MEANS OF |
| EGRESS IS NOT APPLICABLE DUE TO THE BUILDING CODE |
| EXEMPTION. |
| |
| FOR CLARIFICATIONS AND FOR THE OFFICIAL RECORD, PLEASE |
| PROVIDE A DETAILED NARRATIVE OF REVIEW OF THE BUILDING |
| CODE AND IF THE INTENT IS TO INSTALL THIS 2-WAY SYSTEM |
| AS A REQUEST AND NOT A REQUIREMENT. |
| |
| SHOULD THE REVIEW FIND IT IS NOT REQUIRED AND YOU WISH |
| TO WITHDRAWL THIS PERMIT, PLEASE PROVIDE THE APPLICABLE |
| WRITTEN RESPONSE. |
| |
| |
| 1A) IF THE INTENT IS TO PROVIDE THIS 2-WAY SYSTEM EVEN |
| IF EXEMPTED BY THE BUILDING CODE, PLEASE MOVE THE |
| COMMUNICATION METHOD OUT OF THE INDICATED POSTION BY |
| THE ELEVLATORS TO WITHIN THE EXIT STAIRWELL AT THE |
| LANDING. |
| |
| |
| 1B) THERE IS NO COMMAND CENTER/ROOM FOR THIS APRTMENT |
| OCCUPANCY, SO PLEASE PROVIDE THE PROPOSED 24 HOUR |
| EMERGECY CENTRAL CONTROL POINT. IT CAN NOT BE TO 911. |
| |
| |
| |
| 1C) THE 2-WAY CALL BOX DOES NOT APPEAR TO BE REQUIRED |
| ON THE 1ST FLOOR WHERE ACCESSIBLE EGRESS IS AVAILABLE |
| WITHOUT RESTRICTION. |
| |
| PLEASE REVIEW AND CORRECT OR JUSTIFY WITH CODE |
| REFERENCES. |
| |
| |
| 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |