Plan Review Notes
Plan Review Notes For Permit 22030662
Permit Number 22030662
Review Stop Z
Sequence Number 1
Notes
Date Text
2022-09-22 17:02:16INSUFFICIENT
  
 1) PROVIDE A SURVEY, PREPARED BY A FLORIDA LICENSED
 SURVEYOR, THAT SHOWS THE RIGHT-OF-WAY LINE, THE
 SIDEWALK, AND ANY TREES WITHIN THE RIGHT-OF-WAY ALONG
 THE ENTIRE FIBER CONDUIT PATH SO THAT STAFF CAN VERIFY
 THAT THE BORE AND HANDHOLES ARE WITHIN THE
 RIGHT-OF-WAY.
  
 2) HANDHOLES 04+29, 00+64, 03+78, 10+56 AND 10+91 MUST
 BE PLACED WITHIN THE SIDEWALK AND NOT THE PARKWAY.
  
 3) THE CLOSEST EDGE OF THE EXCAVATION/TRENCH FOR
 HANDHOLE 00+64 MUST SHOW A DIMENSION OF AT LEAST TEN
 FEET FROM THE TRUNK OF THE ADJACENT TREES WITHIN THE
 RIGHT-OF-WAY.
  
 4) THE CLOSEST EDGE OF THE EXCAVATION FOR BORE PIT
 07+63 MUST SHOW A DIMENSION OF AT LEAST THREE FEET FROM
 THE TRUNK OF THE ADJACENT PALM TREES. THE BORE MACHINE
 MAY NOT STAGE ADJACENT TO THE PALM TREES.
  
 5) THE TUBULAR MARKERS ARE NOT PERMITTED. MARKERS MAY
 ONLY BE INSTALLED WITHIN THE HANDHOLES OR OTHERWISE
 BURIED.
  
 6) OTHER THAN WHERE THE OPEN TRENCH IS SHOWN CUTTING
 THROUGH THE TREE ROOTS AT HANDHOLE 00+64, THE BORE
 DEPTH IS SUFFICIENT TO AVOID TREE ROOTS.
  