Plan Review Notes For Permit 22030662 |
Permit Number |
22030662 |
|
Review Stop |
Z |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-09-22 17:02:16 | INSUFFICIENT | | | | 1) PROVIDE A SURVEY, PREPARED BY A FLORIDA LICENSED | | SURVEYOR, THAT SHOWS THE RIGHT-OF-WAY LINE, THE | | SIDEWALK, AND ANY TREES WITHIN THE RIGHT-OF-WAY ALONG | | THE ENTIRE FIBER CONDUIT PATH SO THAT STAFF CAN VERIFY | | THAT THE BORE AND HANDHOLES ARE WITHIN THE | | RIGHT-OF-WAY. | | | | 2) HANDHOLES 04+29, 00+64, 03+78, 10+56 AND 10+91 MUST | | BE PLACED WITHIN THE SIDEWALK AND NOT THE PARKWAY. | | | | 3) THE CLOSEST EDGE OF THE EXCAVATION/TRENCH FOR | | HANDHOLE 00+64 MUST SHOW A DIMENSION OF AT LEAST TEN | | FEET FROM THE TRUNK OF THE ADJACENT TREES WITHIN THE | | RIGHT-OF-WAY. | | | | 4) THE CLOSEST EDGE OF THE EXCAVATION FOR BORE PIT | | 07+63 MUST SHOW A DIMENSION OF AT LEAST THREE FEET FROM | | THE TRUNK OF THE ADJACENT PALM TREES. THE BORE MACHINE | | MAY NOT STAGE ADJACENT TO THE PALM TREES. | | | | 5) THE TUBULAR MARKERS ARE NOT PERMITTED. MARKERS MAY | | ONLY BE INSTALLED WITHIN THE HANDHOLES OR OTHERWISE | | BURIED. | | | | 6) OTHER THAN WHERE THE OPEN TRENCH IS SHOWN CUTTING | | THROUGH THE TREE ROOTS AT HANDHOLE 00+64, THE BORE | | DEPTH IS SUFFICIENT TO AVOID TREE ROOTS. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | [email protected] | | | | |
|