Plan Review Notes For Permit 22030607 |
Permit Number |
22030607 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-03-30 12:46:48 | 1ST PLUMBING REVIEW | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | | | 1. PAGE A-9.5 - DETAIL P-1 AND P-2 - BOTH DETAILS SHOW | | THE SHOWER AND WATER CLOSET ON THE HIGH SIDE OF THE | | VENTED FIXTURE CONNECTION TO THE WET VENT. PER THE 2020 | | FRC P3108.2.1 - NOT MORE THAN ONE WET-VENTED FIXTURE | | DRAIN SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED | | FIXTURE CONNECTION. | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | |
|