2022-04-05 17:26:19 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-22030607 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THE NEW |
| ADDITION, SPACES THAT WERE CONVERTED TO CONDITIONED |
| SPACE INCLUDING THE GARAGE. THIS SHOULD SHOW THE GARAGE |
| DOOR. FEC R402 |
| |
| 2) PLEASE SHOW THE ANCHORING OF THE CONDENSING UNITS. |
| FRC M1307.2 |
| |
| 3) PLEASE SHOW THE CONDENSATE DRAIN LINES AND THE |
| TERMINATION LOCATION. FRC 307 |
| |
| 4) PLEASE SHOW THE BATHROOM EXHAUST FANS AND THE |
| EXHAUST TERMINATION LOCATION. FRC 303.3 |
| |
| 5) PLEASE PROVIDE SPECIFICATIONS FOR THE HOOD EXHAUST |
| FAN TO SHOW IT COMPLIES WITH THE MAKE-UP AIR |
| REQUIREMENTS OF FRC M1503.4 |
| |
| 6) PLEASE SHOW THE DRYER EXHAUST AND TERMINATION |
| LOCATION. FRC M1502.3 |
| |
| 7) PLEASE PROVIDE DUCT SIZES AND CFM?S OF AIR FOR THE |
| NEW DUCT WORK AND GRILLES. FBC 107.2.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |