Plan Review Notes
Plan Review Notes For Permit 22030607
Permit Number 22030607
Review Stop E
Sequence Number 1
Notes
Date Text
2022-04-13 10:47:36ELECTRICAL REVIEW FAILED
 1) PLEASE DETAIL INTERIOR LOCATIONS FOR ELECTRIC PANELS
 . FBC 107.2
 2) PLEASE PROVIDE SITE PLAN DETAILING ALL OUTSIDE
 DISCONNECTS AND METERS. FBC 107.2
 3) RISER DIAGRAM DETAILS (3) ELECTRIC PANELS. THE PANEL
 FEEDERS APPEAR TO BE SIZED USING NEC 310.15 (B)(7)(2).
 THESE FEEDERS TO NOT SUPPLY THE ENTIRE LOAD AS OUTLINED
 BY THIS SECTION. THIS SECTION IS NOT APPLICABLE TO SIZE
 THESE FEEDERS. PLEASE CORRECT AND SIZE FEEDERS AS PER
 310.15 TABLES
 4) PLEASE INCLUDE A NOTE WITH DRAWINGS STATING
 GENERATORS, POOL AND SITE LIGHTING ARE UNDER SEPARATE
 PERMITS
 5) PLEASE DETAIL ALL OUTDOOR RECEPTACLES AS PER NEC
 210.50 (E), 210.63 AND 210.64
 6) PLEASE DETAIL ALL RECEPTACLES REQUIRED AS PER 250.50
 (D)
 7) PLEASE DETAIL ARC FAULT PROTECTION COMPLIANCE WITH
 NEC 210.12
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  