2022-04-13 10:47:36 | ELECTRICAL REVIEW FAILED |
| 1) PLEASE DETAIL INTERIOR LOCATIONS FOR ELECTRIC PANELS |
| . FBC 107.2 |
| 2) PLEASE PROVIDE SITE PLAN DETAILING ALL OUTSIDE |
| DISCONNECTS AND METERS. FBC 107.2 |
| 3) RISER DIAGRAM DETAILS (3) ELECTRIC PANELS. THE PANEL |
| FEEDERS APPEAR TO BE SIZED USING NEC 310.15 (B)(7)(2). |
| THESE FEEDERS TO NOT SUPPLY THE ENTIRE LOAD AS OUTLINED |
| BY THIS SECTION. THIS SECTION IS NOT APPLICABLE TO SIZE |
| THESE FEEDERS. PLEASE CORRECT AND SIZE FEEDERS AS PER |
| 310.15 TABLES |
| 4) PLEASE INCLUDE A NOTE WITH DRAWINGS STATING |
| GENERATORS, POOL AND SITE LIGHTING ARE UNDER SEPARATE |
| PERMITS |
| 5) PLEASE DETAIL ALL OUTDOOR RECEPTACLES AS PER NEC |
| 210.50 (E), 210.63 AND 210.64 |
| 6) PLEASE DETAIL ALL RECEPTACLES REQUIRED AS PER 250.50 |
| (D) |
| 7) PLEASE DETAIL ARC FAULT PROTECTION COMPLIANCE WITH |
| NEC 210.12 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| MICHAEL PETERSON |
| ELECTRICAL PLANS EXAMINER |