2022-06-16 16:01:45 | PETER E VALENTI |
| BUILDING PLANS EXAMINER II |
| [email protected] |
| 561 805 6673 |
| |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC M = FBC MECHANICAL |
| FBC FG = FBC FUEL GAS |
| |
| BUILDING REVIEW DENIED: |
| |
| 1.) FBC B 107.2.1, COMPLETE THE DEMO DEBRIS FORM: HTTP: |
| //WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/BUILDI |
| NG-PERMIT-FORMS |
| IF THE FORM IS NOT AVAILABLE ONLINE, PLEASE REQUEST FOR |
| THE FORM. |
| 2.) FBC B 107.2, PROVIDE INFORMATION AS TO HOW THE |
| JOB-SITE RUN-OFF WATER/DEBRIS WILL BE PREVENTED SUCH AS |
| SILT FENCES AND STORM INLET FILTERING. |
| 3.) FBC B 107.2.1, PROVIDE A SEPARATE DRIVEWAY PERMIT. |
| 4.) FBC B 107.2.1, PROVIDE CLARITY AS TO WHICH AREAS OF |
| ATTIC/UNDERSIDE OF ROOF ARE TO RECEIVE BATT INSULATION |
| AND WHICH AREAS ARE TO RECEIVE ICENYNE FOAM SPRAY |
| INSULATION. PLAN SHEETS A7.1 & A7.2 INDICATE SPRAY FOAM |
| INSULATION BUT PLAN SHEET S10.3 INDICATES BATT |
| INSULATION. |
| 5.) FBC B 107.2.1, PROVIDE THE STRUCURAL DETAILS FOR |
| NEW PARAPET WALLS. |
| 6.) FBC B 107.2.1, INDICATE ON PLANS WHICH WALLS & |
| COLUMNS ARE LOAD BEARING AND INDICATE SHORING. |
| 7.) FBC B 107.2.1, PROVIDE DETAILS FOR THE HAND FRAMED |
| WOOD BEAMS AND TRELLIS WORK INCLUDING FASTENERS AND |
| CONNECTORS TO BE USED. |
| 8.) FBC B 107.2.1, PLAN SHEET A0.1 IS MISSING. A |
| DRAINAGE PLAN IS REQUIRED. |
| 9.) FBC B 107.2.1, PLAN SHEET A0.0 APPEARS TO BE THE |
| INDEX SHEET. THIS INDEX DOES NOT INCLUDE ALL PLAN |
| SHEETS: A2.1, A2.2 & A3.3 ARE NOT ON THE INDEX. |
| 10.) FBC B 107.2.1, SEVERAL OF THE PLAN SHEETS HAVE |
| BEEN IDENTIFIED ON THE INDEX AS ARCHITECTURALS BUT ON |
| THE PLAN SHEETS THEY HAVE DIFFERENT SHEET NUMBERS |
| SPECIFIC TO STRUCTURAL, MECHANICAL, ELECTRICAL, & |
| PLUMBING. PLEASE CORRECT THIS SO THEY MATCH. |
| 11.) FBC B 107.2.1, PLAN SHEET A0.0 (COVER SHEET) |
| INDICATES THE COVERED AREA OF THE EXISTING HOUSE IS 427 |
| S.F., PLEASE CLARIFY THE AREA THIS REFERS TO. |
| 12.) FBC B 310, PLAN SHEET A0.0 OCCUPANCY SECTION IS |
| INCOMPLETE. PLEASE INCLUDE THE TYPE OF RESIDENTIAL |
| OCCUPANCY, SUCH AS R-3. |
| 13. FBC B R 806.5, PROVIDE INFORMATION FOR A NON-VENTED |
| ATTIC SPACE AND SHOW WHICH OPTIONS, FROM THE CODE, ARE |
| TO BE USED AS ICENYNE FOAM SPRAY IS INDICATED ON PLAN |
| SHEET A7.1 & A7.2. |
| 14.) FBC B 107.2.1, FBC B 107.3.4.1, PLEASE SUBMIT ALL |
| PRODUCT APPROVALS/MANUFACTURER'S SPECIFICATIONS |
| INCLUDING ROOFING MATERIAL, ICENYNE, TRELLIS CANVAS, |
| GLUE LAMINATE BEAMS, & GARAGE DOOR. IF THESE ITEMS ARE |
| TO BE DEFERRED, PLEASE LIST THEM ON PLAN SHEET. |
| 15.) FBC EC R101.5, PLEASE PROVIDE THE COMPLETED ENERGY |
| CALCULATIONS PER THE ENERGY CONSERVATION CODE. |
| 16.) FBC B 107.2.1, PROVIDE FLAT ROOF DETAILS FOR FLAT |
| ROOF. |
| |