 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. FBC B 107.1 IF THE DESIGN PROFESSIONAL IS AN
 ARCHITECT, INTERIOR DESIGNER, OR ENGINEER LEGALLY
 REGISTERED UNDER THE LAWS OF THE STATE OF FLORIDA
 REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR
 DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA
 STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA
 STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
 2. FBC B 107.2.1. REVISE SUBMITTED FASTENER DENSITY
 CALCULATIONS TO CORRECT EXPOSURE CATEGORY, DESIGN
 PRESSURES & NAILING PATTERNS. PROVIDE CORRECT DESIGN
 PRESSURES AND NAILING PATTERNS FOR ZONE #1 PRIME, ZONE
 #1, ZONE #2 & ZONE #3 AS PER SECTION R301 OF THE 2020
 FBC R. THE CORRECT EXPOSURE FOR THE PROJECT LOCATED AT
 6701 PAMELA LN WEST PALM BEACH IS EXPOSURE CATEGORY D.
 3. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED ROOF SKYLIGHT SYSTEM
 TO BE USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. SECOND
 REQUEST.
 4. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED ROOF RIDGE VENT SYSTEM
 TO BE USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. SECOND
 REQUEST.
 5. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R34
 HAS BEEN REVISED TO FL5259-R35. PLEASE PROVIDE A
 COMPLETE SET; IT COVERS MULTIPLE PRODUCT TYPES; ROOF
 COVER OPTIONS; ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE
 COMBINATIONS, ALLOWABLE SUBSTRATES & ATTACHMENT
 LIMITATIONS. SELECT OPTIONS FROM EACH CATEGORY TO BE
 USED. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE
 CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN
 PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 SECOND REQUEST.
 6. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S). FLAT/LOW
 SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE. SECOND
 REQUEST.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  