Date |
Text |
2022-06-08 13:22:14 | NEW TOWNHOUSE |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) REVISED DRAWING A001 HAS BEEN UPLOADED TO PROJECTDOX |
| ON TOP OF DRAWING A000 - PLEASE FIX |
| |
| 2) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT |
| APPROVAL REQUIRES ADDITIONAL SIGNED AND SEALED |
| ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR |
| ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE |
| (PER DRAWING S-7) THAN THE MAXIMUM SHOWN ON THE PRODUCT |
| APPROVAL (-52.5) - SEE NOTE NUMBER 9 ON THE PRODUCT |
| APPROVAL. |
| |
| 3) PLEASE PROVIDE THE SMART FLOOD VENT PRODUCT APPROVAL |
| OR ICC EVALUATION CERTIFICATE. |
| |
| 4) ELEVATION CERTIFICATES NEED CORRECTIONS - |
| |
| A) A9(A) INCORRECT SQUARE FOOTAGE OF THE GARAGE SHOWN. |
| B) A9(B) INCORRECT NUMBER OF FLOOD VENTS SHOWN. |
| C) A9(C) PLEASE SHOW THE TOTAL SQUARE INCHES OF FLOOD |
| OPENINGS. |
| D) A9(D) SMART VENTS ARE ENGINEERED VENTS - SHOULD BE |
| MARKED "YES". |
| |
| 5) SITE PLAN SHOULD SHOW THE SITE DRAINAGE - OR PROVIDE |
| THE CIVIL STORM WATER DRAINAGE PLAN - |
| FBC WPB 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS |
| SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE |
| ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE |
| AND LOCATION OF NEW CONSTRUCTION AND EXISTING |
| STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE |
| ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED |
| GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS |
| APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN |
| FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE |
| WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE |
| SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED |
| WATER RETAINING SWALES) |
| |
| 6) "PLUNGE POOL" - BARRIER SHOULD SURROUND THE POOL - |
| THE GATE ON THE SIDE UNITS NEEDS TO BE SELF-CLOSING AND |
| LATCHING PER FBC R4501.17.1.8 |
| ACCESS GATES, WHEN PROVIDED, SHALL BE SELF-CLOSING AND |
| SHALL COMPLY WITH THE REQUIREMENTS OF SECTIONS |
| R4501.17.1.1 THROUGH R4501.17.1.7 AND SHALL BE EQUIPPED |
| WITH A SELF-LATCHING LOCKING DEVICE LOCATED ON THE POOL |
| SIDE OF THE GATE. WHERE THE DEVICE RELEASE IS LOCATED |
| NO LESS THAN 54 INCHES (1372 MM) FROM THE BOTTOM OF THE |
| GATE, THE DEVICE RELEASE MECHANISM MAY BE LOCATED ON |
| EITHER SIDE OF THE GATE AND SO PLACED THAT IT CANNOT BE |
| REACHED BY A YOUNG CHILD OVER THE TOP OR THROUGH ANY |
| OPENING OR GAP FROM THE OUTSIDE. GATES THAT PROVIDE |
| ACCESS TO THE SWIMMING POOL MUST OPEN OUTWARD AWAY FROM |
| THE POOL. THE GATES AND BARRIER SHALL HAVE NO OPENING |
| GREATER THAN 1/2 INCH (12.7 MM) WITHIN 18 INCHES (457 |
| MM) OF THE RELEASE MECHANISM. |
| |