Plan Review Notes
Plan Review Notes For Permit 22030459
Permit Number 22030459
Review Stop B
Sequence Number 2
Notes
Date Text
2022-06-08 13:22:14NEW TOWNHOUSE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) REVISED DRAWING A001 HAS BEEN UPLOADED TO PROJECTDOX
 ON TOP OF DRAWING A000 - PLEASE FIX
  
 2) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT
 APPROVAL REQUIRES ADDITIONAL SIGNED AND SEALED
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE
 (PER DRAWING S-7) THAN THE MAXIMUM SHOWN ON THE PRODUCT
 APPROVAL (-52.5) - SEE NOTE NUMBER 9 ON THE PRODUCT
 APPROVAL.
  
 3) PLEASE PROVIDE THE SMART FLOOD VENT PRODUCT APPROVAL
 OR ICC EVALUATION CERTIFICATE.
  
 4) ELEVATION CERTIFICATES NEED CORRECTIONS -
  
 A) A9(A) INCORRECT SQUARE FOOTAGE OF THE GARAGE SHOWN.
 B) A9(B) INCORRECT NUMBER OF FLOOD VENTS SHOWN.
 C) A9(C) PLEASE SHOW THE TOTAL SQUARE INCHES OF FLOOD
 OPENINGS.
 D) A9(D) SMART VENTS ARE ENGINEERED VENTS - SHOULD BE
 MARKED "YES".
  
 5) SITE PLAN SHOULD SHOW THE SITE DRAINAGE - OR PROVIDE
 THE CIVIL STORM WATER DRAINAGE PLAN -
 FBC WPB 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS
 SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE
 ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE
 AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES)
  
 6) "PLUNGE POOL" - BARRIER SHOULD SURROUND THE POOL -
 THE GATE ON THE SIDE UNITS NEEDS TO BE SELF-CLOSING AND
 LATCHING PER FBC R4501.17.1.8
 ACCESS GATES, WHEN PROVIDED, SHALL BE SELF-CLOSING AND
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTIONS
 R4501.17.1.1 THROUGH R4501.17.1.7 AND SHALL BE EQUIPPED
 WITH A SELF-LATCHING LOCKING DEVICE LOCATED ON THE POOL
 SIDE OF THE GATE. WHERE THE DEVICE RELEASE IS LOCATED
 NO LESS THAN 54 INCHES (1372 MM) FROM THE BOTTOM OF THE
 GATE, THE DEVICE RELEASE MECHANISM MAY BE LOCATED ON
 EITHER SIDE OF THE GATE AND SO PLACED THAT IT CANNOT BE
 REACHED BY A YOUNG CHILD OVER THE TOP OR THROUGH ANY
 OPENING OR GAP FROM THE OUTSIDE. GATES THAT PROVIDE
 ACCESS TO THE SWIMMING POOL MUST OPEN OUTWARD AWAY FROM
 THE POOL. THE GATES AND BARRIER SHALL HAVE NO OPENING
 GREATER THAN 1/2 INCH (12.7 MM) WITHIN 18 INCHES (457
 MM) OF THE RELEASE MECHANISM.
  