2022-03-25 08:56:291ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22030459
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AN ENERGY CALCULATION MUST BE SUBMITTED FOR EACH
 TOWN HOUSE, THIS SUBMITTAL MUST INCLUDE THE ADDRESS FOR
 EACH TOWNHOME. FBC EC R402
  
 2) A MECHANICAL EQUIPMENT SIZING CALCULATION MUST BE
 SUBMITTED FOR EACH TOWN HOUSE. FBC EC R403.7
  
 3) THE PERMIT APPLICATION MUST HAVE THE CORRECT ADDRESS
 FOR EACH TOWN HOUSE. FBC 107.2.1
  
 4) EACH TOWN HOUSE MUST HAVE A SEPARATE PERMIT
 APPLICATION. THE PERMIT APPLICATIONS ?WORK DESCRIPTION?
 STATES NEW CONSTRUCTION OF 7 TOWNHOUSES ON EACH
 APPLICATION SUBMITTED. PLEASE SHOW THAT EACH
 APPLICATION IS FOR A SPECIFIC ADDRESS AND PROJECT FOR
 THAT ADDRESS. FBC 107.2.1
  
 5) UNIT SHEETS: KEYNOTE 3 SPECS OUT A RE-CIRCULATING
 TYPE RANGE HOOD BUT IN THE SUPPORTING DOCUMENTS THERE
 IS A 600 CFM HOOD EXHAUST FAN. PLEASE EITHER SHOW THE
 DUCTWORK FOR THE HOOD AND THE TERMINATION LOCATION OR
 REMOVE THE 600 CFM HOOD MOTOR IN THE SUPPORTING
 DOCUMENTS FOR THIS SUBMITTAL. FBC 107.2.1
  
 6) PLEASE PROVIDE VENTILATION REQUIREMENTS FROM THE
 MANUFACTURER FOR THE POOL MOTOR AND POOL PUMPS THAT ARE
 LOCATED IN THE GARAGES. FBC 107.2.1
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  