2022-03-25 08:56:29 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-22030459 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) AN ENERGY CALCULATION MUST BE SUBMITTED FOR EACH |
| TOWN HOUSE, THIS SUBMITTAL MUST INCLUDE THE ADDRESS FOR |
| EACH TOWNHOME. FBC EC R402 |
| |
| 2) A MECHANICAL EQUIPMENT SIZING CALCULATION MUST BE |
| SUBMITTED FOR EACH TOWN HOUSE. FBC EC R403.7 |
| |
| 3) THE PERMIT APPLICATION MUST HAVE THE CORRECT ADDRESS |
| FOR EACH TOWN HOUSE. FBC 107.2.1 |
| |
| 4) EACH TOWN HOUSE MUST HAVE A SEPARATE PERMIT |
| APPLICATION. THE PERMIT APPLICATIONS ?WORK DESCRIPTION? |
| STATES NEW CONSTRUCTION OF 7 TOWNHOUSES ON EACH |
| APPLICATION SUBMITTED. PLEASE SHOW THAT EACH |
| APPLICATION IS FOR A SPECIFIC ADDRESS AND PROJECT FOR |
| THAT ADDRESS. FBC 107.2.1 |
| |
| 5) UNIT SHEETS: KEYNOTE 3 SPECS OUT A RE-CIRCULATING |
| TYPE RANGE HOOD BUT IN THE SUPPORTING DOCUMENTS THERE |
| IS A 600 CFM HOOD EXHAUST FAN. PLEASE EITHER SHOW THE |
| DUCTWORK FOR THE HOOD AND THE TERMINATION LOCATION OR |
| REMOVE THE 600 CFM HOOD MOTOR IN THE SUPPORTING |
| DOCUMENTS FOR THIS SUBMITTAL. FBC 107.2.1 |
| |
| 6) PLEASE PROVIDE VENTILATION REQUIREMENTS FROM THE |
| MANUFACTURER FOR THE POOL MOTOR AND POOL PUMPS THAT ARE |
| LOCATED IN THE GARAGES. FBC 107.2.1 |
| |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |