Plan Review Notes
Plan Review Notes For Permit 22030459
Permit Number 22030459
Review Stop G
Sequence Number 1
Notes
Date Text
2022-03-25 10:48:4903/25/22 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1. PLEASE PLACE A NOT ON PLANS.
  
 2. WOULD YOU PLEASE SUBMIT EACH LENGTH OF ALL CUT
 SECTIONS OF PIPE ON THE ISOMETRIC DRAWING PER 2020 FBC
 RES. SECS. G2413.4.1, G2413.4.2.
  
 3. IS THE POOL HEATER IN A GARAGE? WOULD YOU PLEASE
 SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE FBC RES.
 SEC. G2407.1 AND G2439.4. IF THE LOUVER IS USED, SHOW
 THE LOUVERS' LOCATIONS THAT ARE BEING INSTALLED FOR THE
 COMBUSTION AIR. THE LOUVERS CANNOT BE LOCATED ON AN
 EXTERIOR WALL THAT IS FIRE RATED AS THE FIRE RATING OF
 THE WALL MUST BE MAINTAINED PER THE WPB AMENDMENTS TO
 FBC SEC.107.2.1. PLEASE PROVIDE VENTING DIAGRAMS
 SHOWING THE TYPE AND SIZE OF GAS VENTS, GAS VENT RUNS,
 AND TERMINATION LOCATIONS FOR POOL HEATER PER THE 2020
 FBC FG SEC. 503.
  
 4. SHOW THE DISTANCE FROM THE POINT OF THE DELIVERY GAS
 METER TO THE MOST REMOTE OUTLET IN THE BUILDING AND/OR
 SYSTEM PER THE 2020 FBC RES. SEC. G2413.4.1.
  
 5. LIST THE BTU LOAD OF EACH APPLIANCE WITH THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC RES. SEC.
 G2413.
  
 6. WOULD YOU PLEASE PROVIDE WHAT TYPE OF GAS (LP OR
 NATURAL) IS BEING USED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. INDICATE THE SYSTEM'S DELIVERY PRESSURE (PSI) ON THE
 PLAN PER THE 2020 FBC RES. SEC. G2413.2.
  
 8. WOULD YOU PLEASE PROVIDE MANUFACTURES SPECIFICATIONS
 FOR ALL EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC
 RES. SEC. G2408.1. GAS APPLIANCES SHALL BE LISTED AND
 LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION PER THE 2020 FBC RES. SEC. G2413.2 AND
 G2404.3.
  
 9. A GAS GRILL IS LABELED FOR OUTDOOR USE, AND IT SEEMS
 TO BE IN A COVERED PATIO; IF SO, PLEASE PROVIDE
 MANUFACTURERS RECOMMENDATION FOR A VENTILATION HOOD PER
 THE 2020 FG 305.1 OR 2020 FBC RES. SEC. G2408.1. A
 SEPARATE PERMIT MAY BE REQUIRED FOR HOOD PER THE WPB
 AMENDMENTS TO THE FBC SEC. 105.1.
  
 10. WOULD YOU PLEASE LABEL THE SHUTOFF VALVES AND DRIP
 LEGS ON GAS ISOMERIC PER THE 2020 FBC RES. SEC. G2420.5
 AND SHOW SHUT OFF ON THE MAIN METER, PLEASE.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  