2022-03-25 10:48:49 | 03/25/22 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 105.1. PLEASE PLACE A NOT ON PLANS. |
| |
| 2. WOULD YOU PLEASE SUBMIT EACH LENGTH OF ALL CUT |
| SECTIONS OF PIPE ON THE ISOMETRIC DRAWING PER 2020 FBC |
| RES. SECS. G2413.4.1, G2413.4.2. |
| |
| 3. IS THE POOL HEATER IN A GARAGE? WOULD YOU PLEASE |
| SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE FBC RES. |
| SEC. G2407.1 AND G2439.4. IF THE LOUVER IS USED, SHOW |
| THE LOUVERS' LOCATIONS THAT ARE BEING INSTALLED FOR THE |
| COMBUSTION AIR. THE LOUVERS CANNOT BE LOCATED ON AN |
| EXTERIOR WALL THAT IS FIRE RATED AS THE FIRE RATING OF |
| THE WALL MUST BE MAINTAINED PER THE WPB AMENDMENTS TO |
| FBC SEC.107.2.1. PLEASE PROVIDE VENTING DIAGRAMS |
| SHOWING THE TYPE AND SIZE OF GAS VENTS, GAS VENT RUNS, |
| AND TERMINATION LOCATIONS FOR POOL HEATER PER THE 2020 |
| FBC FG SEC. 503. |
| |
| 4. SHOW THE DISTANCE FROM THE POINT OF THE DELIVERY GAS |
| METER TO THE MOST REMOTE OUTLET IN THE BUILDING AND/OR |
| SYSTEM PER THE 2020 FBC RES. SEC. G2413.4.1. |
| |
| 5. LIST THE BTU LOAD OF EACH APPLIANCE WITH THE TOTAL |
| BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC RES. SEC. |
| G2413. |
| |
| 6. WOULD YOU PLEASE PROVIDE WHAT TYPE OF GAS (LP OR |
| NATURAL) IS BEING USED PER THE WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 7. INDICATE THE SYSTEM'S DELIVERY PRESSURE (PSI) ON THE |
| PLAN PER THE 2020 FBC RES. SEC. G2413.2. |
| |
| 8. WOULD YOU PLEASE PROVIDE MANUFACTURES SPECIFICATIONS |
| FOR ALL EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC |
| RES. SEC. G2408.1. GAS APPLIANCES SHALL BE LISTED AND |
| LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| INSPECTION PER THE 2020 FBC RES. SEC. G2413.2 AND |
| G2404.3. |
| |
| 9. A GAS GRILL IS LABELED FOR OUTDOOR USE, AND IT SEEMS |
| TO BE IN A COVERED PATIO; IF SO, PLEASE PROVIDE |
| MANUFACTURERS RECOMMENDATION FOR A VENTILATION HOOD PER |
| THE 2020 FG 305.1 OR 2020 FBC RES. SEC. G2408.1. A |
| SEPARATE PERMIT MAY BE REQUIRED FOR HOOD PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 105.1. |
| |
| 10. WOULD YOU PLEASE LABEL THE SHUTOFF VALVES AND DRIP |
| LEGS ON GAS ISOMERIC PER THE 2020 FBC RES. SEC. G2420.5 |
| AND SHOW SHUT OFF ON THE MAIN METER, PLEASE. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON |
| REQUEST. |
| |