Plan Review Notes
Plan Review Notes For Permit 22030326
Permit Number 22030326
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2022-07-06 10:51:06CONSIDER THE FOLLOWING COMMENTS AS PROVISO
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 INSTALATION OF FIRE SPRINKLER SYSTEM IS REQUIRED TO BE
 COMPLETED BY A CERTIFIED FIRE SPRINKLER CONTRACTOR AND
 SHALL COMPLY WITH NFPA 13. SEPARATE SHOP DRAWINGS, ARE
 REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY THE
 FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE SYSTEM.
  
 PLEASE ADDRESS FIRE SPRINKLERS MORE SPECICALLY IN PLAN
 SET.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]