Plan Review Notes
Plan Review Notes For Permit 22030326
Permit Number 22030326
Review Stop B
Sequence Number 1
Notes
Date Text
2022-04-20 14:50:28BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE RAMP HEIGHT TO COMPLY WITH FBC 405.6
 RISE. THE RISE FOR ANY RAMP RUN SHALL BE 30 INCHES (760
 MM) MAXIMUM.
  
 2) RAMP IS SUBJECT TO WIND LOADS - PLEASE PROVIDE RAMP
 DETAILS FROM A DESIGN PROFESSIONAL - SHOWING THE
 FOUNDATION, TIE DOWNS AND THE WIND DESIGN DATA USED -
 FBC 1603.1.4
  
 3) PLEASE SHOW THE WIND DESIGN DATA USED ON THE
 DRAWINGS FBC 1603.1.4
  
 4) PLEASE SHOW THE CALCULATIONS FOR THE EXTERIOR
 OPENINGS THAT ARE CLOSE TO THE PROPERTY LINES FBC E
 1012.6.3 OPENING PROTECTIVES.
 OPENINGS IN EXTERIOR WALLS SHALL BE PROTECTED AS
 REQUIRED BY THE FLORIDA BUILDING CODE, BUILDING. WHERE
 OPENINGS IN THE EXTERIOR WALLS ARE REQUIRED TO BE
 PROTECTED BECAUSE OF THEIR DISTANCE FROM THE LOT LINE,
 THE SUM OF THE AREA OF SUCH OPENINGS SHALL NOT EXCEED
 50 PERCENT OF THE TOTAL AREA OF THE WALL IN EACH STORY.
  
 5) PLEASE SHOW THE EXISTING OCCUPANCY CLASSIFICATION
 FBC E 1012.6
  
 6) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE NEW EXTERIOR DOORS, EXTERIOR
 WINDOWS, ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED
 TO BE REVIEWED AND APPROVED BY THE DESIGNER OF RECORD
 FBC WPB 107.3.4
  
 7) ACCESSIBLE RESTROOMS - PLEASE STATE THAT THE MIRROR
 DIMENSIONS FROM THE FLOOR ARE TO THE "REFLECTIVE
 SURFACE" - FBC A 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 8) ACCESSIBLE RESTROOM - PLEASE SHOW THE REAR GRAB BAR
 DIMENSIONS FROM THE CENTER OF THE TOILET NOT THE WALL -
 FBC A 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 9) ACCESSIBLE RESTROOM - PLEASE SHOW THE DIMENSION FOR
 THE TOILET PAPER HOLDER FROM THE FACE OF THE TOILET -
 FBC 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 10) ACCESSIBLE SHOWER - PLEASE SHOW GRAB BARS ON ALL
 WALLS PER FBC 608.3.2 STANDARD ROLL-IN TYPE SHOWER
 COMPARTMENTS.
 WHERE A SEAT IS PROVIDED IN STANDARD ROLL-IN TYPE
 SHOWER COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THE
 BACK WALL AND THE SIDE WALL OPPOSITE THE SEAT. GRAB
 BARS SHALL NOT BE PROVIDED ABOVE THE SEAT. WHERE A SEAT
 IS NOT PROVIDED IN STANDARD ROLL-IN TYPE SHOWER
 COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THREE
 WALLS. GRAB BARS SHALL BE INSTALLED 6 INCHES (150 MM)
 MAXIMUM FROM ADJACENT WALLS.
  
 11) CANOPY DETAILS, ALUMINUM RAMP DETAILS, AND PRODUCT
 APPROVALS FOR WINDOWS, DOORS AND ROOFING SYSTEMS - ETC.
 MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS TO BE
 DEFERRED ON THE CONSTRUCTION DOCUMENTS - 107.3.4.1
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED
 SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL
 WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  
  