 PAGES E2.5 AND E2.6 SHOW CAR CHARGERS BUT ON PANEL
 SCHEDULE THEY ARE SHOWN AS FUTURE? PLEASE COORDINATE.
  
 AGAIN VALUE FOR NEW HPACC PANEL AND THE CHARGERS 22,5K
  
 PAGE E7.7 WHICH CARGER ARE YOU USING? SPECS DO NOT LIST
 ELECTRICAL REQUIREMENTS FOR THE CHARGERS.
  
 PAGE E7.6 PANEL HPACC LOAD FOR CAR CHARGERS ARE TO BE
 DONE AT 125% 625.41
  
  