Plan Review Notes For Permit 22030314 |
Permit Number |
22030314 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-04-04 14:56:00 | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER | | 561-805-6713 | | [email protected] | | | | 1) FIRE PUMP, IS IT ELECTRIC? NOT SHOWN ON RISER | | DIAGRAM. 215.5 | | | | 2) E-1.1 NEW PANEL HPACC IS THIS OVERHEAD? IF SO MAIN | | REQUIRED OUTSIDE OF BUILDING OR ENCASED IN 2" OF | | CONCRETE. | | | | 3) E1.1 ALL THESE SERVICES WILL NEED TO BE MAPED OUT | | AND PLAQUED FOR LIFE SAFETY REASONS. 230.3(E) | | | | 4) SERVICES LABELED B-2.1, A-1.1, C-1.1, C-2.1 NEED TO | | ADDRESS COMPLIANCE WITH 240.87 ARC FLASH MITIGATION. | | | | 5) VALUE OF REVISION IS $0, PLEASE UPDATE VALUE FOR | | ADDED SYSTEMS CAR CHARGERS, TWH, PANEL CB. |
|