2022-03-21 13:03:501ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22030297
 3/21/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) G102 & G103: THE FLORIDA ACCESSIBILITY CODE 7TH
 EDITION 2020 IS THE GOVERNING CODE LISTED ON G103
 HOWEVER THE FOLLOWING ITEMS ON G102 ARE NOT CONSISTENT
 WITH THE CODE.
 A) WATER CLOSET GRAB BAR HEIGHTS MEASURED TO THE
 CENTERLINE OF THE GRAB BARS AND NOT THE TOPS OF THE
 GRIPPING SURFACES- SEC. 609.4.
 B) MIRROR MEASUREMENT TO THE FRAME AND NOT THE
 REFLECTIVE SURFACE- SEC. 603.3.
 C) TYPE A LAVATORY OVERLAP IS NOT A TERM USED IN THE
 FBC ACC CODE HOWEVER THE DETAIL IS CONSISTENT WITH SEC.
 604.3.2.
  
 2) G102, G103, A200 & A201: THE APPLICATION FOR THE
 PROJECT INDICATES MODIFICATIONS OF 5 UNITS TO MEET UFAS
 STANDARDS, HOWEVER THERE IS NO REFERENCE TO THE UFAS ON
 THE PLANS AND NO DETAILS- SEC. 107.2.1 WPB. PLEASE
 PROVIDE MORE INFORMATION OR DOCUMENTS TO CLARIFY HOW
 THE SCOPE OF THE ACCESSIBILITY WORK WAS DETERMINED.
  
 3) A200 & A201: PROVIDE THE FOLLOWING LIST OF FBC ACC
 COMPLIANCE DETAILS:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SEC. 606.2.
 C) THE REAR GRAB BAR FOR THE WATER CLOSET TO BE 36
 INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF
 THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24
 INCHES MINIMUM ON THE OTHER SIDE- SEC. 604.5.2. (SEE
 DETAIL ON G102).
 D) DIMENSIONS OF THE SHOWER- SEC. 608.2.2.
 E) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 SHOWER- SECTION 608.2.2.1.
 F) SHOWER GRAB HEIGHTS MEASURED TO THE CENTERLINE OF
 THE GRAB BARS AND NOT THE TOPS OF THE GRIPPING
 SURFACES- SEC. 609.4.
 G) HEIGHT OF THE SHOWER SEAT- SEC. 610.3
 H) DIMENSIONS AND CLEARANCES FOR THE SEAT- SEE SEC.
 610.3, AND SEC. AND FIGURE 610.3.2.
  
 4) A200 & A201: FHA TYPE B BATHROOMS ARE SPECIFIED
 HOWEVER THE LAYOUTS WILL NOT PROVIDE THE REQUIRED CLEAR
 FLOOR SPACE APPROACH FOR THE BATHTUB AS SHOWN IN
 FIGURES 7(B) FHAG- FBC ACC, AND AS SHOWN ON PAGE 7.53
 FHA DESIGN MANUAL- SPECIFICATION B. THE CURRENT LAYOUT
 SHOWING THE WATER CLOSET BY THE BATHTUB IS CONSISTENT
 WITH A SPECIFICATION A COMPLIANCE.
 A) PLEASE SHOW THE TOTAL WIDTH AND LENGTH MEASUREMENTS
 OF THE TYPE B BATHROOMS.
 B) SHOW THE CLEAR FLOOR DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- PAGE 7.43- 7.44 FHA DESIGN MANUAL, AND
 FIGURE 6A FHAG- FBC ACC.
 C) SHOW THE CLEAR FLOOR DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- PAGE 7.47- 7.52 FHA DESIGN MANUAL, AND
 FIGURE 6C FHAG- FBC ACC.
 D) PROVIDE A DETAIL FOR THE REMOVABLE LAVATORY CABINET-
 PAGE 7.49 FHA DESIGN MANUAL.
 E) SHOW THE FUTURE GRAB BAR LOCATIONS FOR THE WATER
 CLOSET AND BATHTUB AND PROVIDE REINFORCEMENT DETAILS-
 SEE PAGES 6.1- 6.9 FHA DESIGN MANUAL, AND FIGURES 3 & 4
 FHAG- FBC ACC.
  
 5) A200 & A201: PROVIDE A DETAIL FOR THE REMOVABLE
 KITCHEN SINK FRONT- PAGE 7.12 FHAG- FBC ACC.
  
 6) P101: PROVIDE WASTE AND VENT ISOMETRIC DRAWINGS FOR
 THE KITCHEN SINKS- SEC. 107.3.5.1.3 WPB.
  
 7) P101: CORRECT THE NOTE AT ISOMETRIC- 2 DETAIL- THE
 2-INCH FIXTURE DRAIN FOR THE WASHING MACHINE SHALL
 CONNECT TO A MINIMUM 3-INCH DIAMETER BRANCH OR STACK-
 SEC. 406.2 FBC P.
  
 8) P101: SHOW WATER HAMMER ARRESTOR LOCATIONS- SEC.
 604.9 FBC P.
  
 9) P101: PROVIDE A SHOWER PAN DETAIL- SEC. 421.5-
 412.5.2.6 FBC P.
  
 10) P101: PROVIDE SLAB REPAIR AND FIRESTOPPING DETAILS
 FOR PIPE PENETRATIONS- SEC. 107.2.1 WPB, AND SEC. 315.1
 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  