Plan Review Notes
Plan Review Notes For Permit 22030297
Permit Number 22030297
Review Stop E
Sequence Number 1
Notes
Date Text
2022-04-11 10:36:41ELECTRIC REVIEW FAILED
 1) THE CODE ANALYSYS SHEET STATES THIS IS A LEVEL 1
 ALTERATION, IT APPEARS FROM THE WORK SCOPE THAT THIS IS
 A LEVEL 2 ALTERATION. PLEASE CLARIFY . FBC EXISTING
 BUILDING 602.1 AND 603.1
 2) IF CLASSIFIED AS A LEVEL 2 THEN ARC FAULT CIRCUIRT
 PROTECTION SHALL BE REQUIRED AS WELL AS OTHER
 REQUIREMENTS OF THE NEC AS REQUIRED. NEC 210.12 AND NEC
 2017
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  