Date |
Text |
2022-08-02 10:59:10 | CREATING 2 UNITS |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) PLEASE SHOW STAIR HAND RAIL EXTENSION AT THE BOTTOM |
| OF THE STAIRS TO SLOPE PER FBC 1014.6 HANDRAIL |
| EXTENSIONS. |
| HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING |
| SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN |
| ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS |
| ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL |
| EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM) |
| BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE |
| DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER. |
| |
| 2) ACCESSIBLE RESTROOM = PLEASE USE THE WORDS |
| "REFLECTIVE SURFACE" WHEN SHOWING THE DIMENSION FROM |
| THE FLOOR TO THE BOTTOM OF THE MIRROR - FBC A 603.3 |
| MIRRORS. |
| MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND. |
| |
| 3) ACCESSIBLE RESTROOM = PLEASE SHOW THE TOILET PAPER |
| DISPENSER DIMENSIONS FROM THE FRONT OF THE TOILET AND |
| HEIGHT FROM THE FLOOR - FBC A 604.7 DISPENSERS. |
| TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 |
| INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND |
| SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL |
| NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES |
| NOT ALLOW CONTINUOUS PAPER FLOW. |
| |
| 4) PLEASE SHOW THE RAMP EDGE PROTECTION (SHOW THE GUARD |
| RAIL BOTTOM RAIL WITHIN 4" OF THE RAMP) FBC A 405.9 |
| EDGE PROTECTION. |
| EDGE PROTECTION COMPLYING WITH 405.9.1 OR 405.9.2 SHALL |
| BE PROVIDED ON EACH SIDE OF RAMP RUNS AND AT EACH SIDE |
| OF RAMP LANDINGS. 405.9.2CURB OR BARRIER. |
| A CURB OR BARRIER SHALL BE PROVIDED THAT PREVENTS THE |
| PASSAGE OF A 4 INCH (100 MM) DIAMETER SPHERE, WHERE ANY |
| PORTION OF THE SPHERE IS WITHIN 4 INCHES (100 MM) OF |
| THE FINISH FLOOR OR GROUND SURFACE. |
| |
| 5) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| PRODUCT APPROVALS FOR THE EXTERIOR STOREFRONT WINDOWS |
| AND DOORS - ALL PRODUCT APPROVALS NEED TO BE REVIEWED |
| AND MARKED APPROVED BY THE DESIGNER OF RECORD FBC WPB |
| 107.3.4 |
| |
| 6) CANNOT REUSE STOREFRONT WINDOWS UNLESS YOU HAVE A |
| CURRENT PRODUCT APPROVAL FOR THEM - FBC EXISTING 707.4 |
| REPLACEMENT OF WINDOWS AND DOORS. |
| THE REPLACEMENT OF GARAGE DOORS, EXTERIOR DOORS, |
| SKYLIGHTS, AND OPERATIVE AND INOPERATIVE WINDOWS SHALL |
| BE DESIGNED AND CONSTRUCTED TO COMPLY WITH CHAPTER 16 |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 7) ELEVATION CERTIFICATE PROVIDED IS INCORRECT - PALM |
| BEACH COUNTY FLOOD MAP SHOWS BUILDING IN A FLOOD ZONE |
| (AE 12.10) - NFIP - JOB IS A SUBSTANTIAL IMPROVEMENT |
| JOB VALUE + 5 YEAR ACCUMULATION = 1,015,272.00 - |
| BUILDING VALUE = 1,355,080.00 - THE BUILDING LOWEST |
| FLOOR ELEVATION NEEDS TO BE AT 14.10 NAVD - PLEASE |
| PROVIDE AN ELEVATION CERTIFICATE TO VERIFY THE LOWEST |
| FLOOR ELEVATION - ORDINANCE NO. 4729-17 SEC. 18-35 (A) |
| AND (B) |