Plan Review Notes
Plan Review Notes For Permit 22030290
Permit Number 22030290
Review Stop B
Sequence Number 2
Notes
Date Text
2022-08-02 10:59:10CREATING 2 UNITS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW STAIR HAND RAIL EXTENSION AT THE BOTTOM
 OF THE STAIRS TO SLOPE PER FBC 1014.6 HANDRAIL
 EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS
 ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL
 EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM)
 BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE
 DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER.
  
 2) ACCESSIBLE RESTROOM = PLEASE USE THE WORDS
 "REFLECTIVE SURFACE" WHEN SHOWING THE DIMENSION FROM
 THE FLOOR TO THE BOTTOM OF THE MIRROR - FBC A 603.3
 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 3) ACCESSIBLE RESTROOM = PLEASE SHOW THE TOILET PAPER
 DISPENSER DIMENSIONS FROM THE FRONT OF THE TOILET AND
 HEIGHT FROM THE FLOOR - FBC A 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 4) PLEASE SHOW THE RAMP EDGE PROTECTION (SHOW THE GUARD
 RAIL BOTTOM RAIL WITHIN 4" OF THE RAMP) FBC A 405.9
 EDGE PROTECTION.
 EDGE PROTECTION COMPLYING WITH 405.9.1 OR 405.9.2 SHALL
 BE PROVIDED ON EACH SIDE OF RAMP RUNS AND AT EACH SIDE
 OF RAMP LANDINGS. 405.9.2CURB OR BARRIER.
 A CURB OR BARRIER SHALL BE PROVIDED THAT PREVENTS THE
 PASSAGE OF A 4 INCH (100 MM) DIAMETER SPHERE, WHERE ANY
 PORTION OF THE SPHERE IS WITHIN 4 INCHES (100 MM) OF
 THE FINISH FLOOR OR GROUND SURFACE.
  
 5) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR STOREFRONT WINDOWS
 AND DOORS - ALL PRODUCT APPROVALS NEED TO BE REVIEWED
 AND MARKED APPROVED BY THE DESIGNER OF RECORD FBC WPB
 107.3.4
  
 6) CANNOT REUSE STOREFRONT WINDOWS UNLESS YOU HAVE A
 CURRENT PRODUCT APPROVAL FOR THEM - FBC EXISTING 707.4
 REPLACEMENT OF WINDOWS AND DOORS.
 THE REPLACEMENT OF GARAGE DOORS, EXTERIOR DOORS,
 SKYLIGHTS, AND OPERATIVE AND INOPERATIVE WINDOWS SHALL
 BE DESIGNED AND CONSTRUCTED TO COMPLY WITH CHAPTER 16
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 7) ELEVATION CERTIFICATE PROVIDED IS INCORRECT - PALM
 BEACH COUNTY FLOOD MAP SHOWS BUILDING IN A FLOOD ZONE
 (AE 12.10) - NFIP - JOB IS A SUBSTANTIAL IMPROVEMENT
 JOB VALUE + 5 YEAR ACCUMULATION = 1,015,272.00 -
 BUILDING VALUE = 1,355,080.00 - THE BUILDING LOWEST
 FLOOR ELEVATION NEEDS TO BE AT 14.10 NAVD - PLEASE
 PROVIDE AN ELEVATION CERTIFICATE TO VERIFY THE LOWEST
 FLOOR ELEVATION - ORDINANCE NO. 4729-17 SEC. 18-35 (A)
 AND (B)