Plan Review Notes
Plan Review Notes For Permit 22030290
Permit Number 22030290
Review Stop B
Sequence Number 1
Notes
Date Text
2022-05-05 15:41:39CREATING 2 UNITS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE MOP SINK WALLS TO COMPLY WITH FBC
 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR,
  
 2) PLEASE SHOW STAIR HAND RAIL HEIGHT PER FBC 1014.2
 HEIGHT.
 HANDRAIL HEIGHT, MEASURED ABOVE STAIR TREAD NOSINGS, OR
 FINISH SURFACE OF RAMP SLOPE, SHALL BE UNIFORM, NOT
 LESS THAN 34 INCHES (864 MM) AND NOT MORE THAN 38
 INCHES (965 MM).
  
 3) PLEASE SHOW STAIR HAND RAIL EXTENSION AT THE BOTTOM
 OF THE STAIRS TO SLOPE PER FBC 1014.6 HANDRAIL
 EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS
 ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL
 EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM)
 BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE
 DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER.
  
 4) PLEASE SHOW THE STAIR RISER HEIGHT AND TREAD DEPTHS
 TO COMPLY WITH FBC 1011.5.2 RISER HEIGHT AND TREAD
 DEPTH.
 STAIR RISER HEIGHTS SHALL BE 7 INCHES (178 MM) MAXIMUM
 AND 4 INCHES (102 MM) MINIMUM. THE RISER HEIGHT SHALL
 BE MEASURED VERTICALLY BETWEEN THE NOSINGS OF ADJACENT
 TREADS. RECTANGULAR TREAD DEPTHS SHALL BE 11 INCHES
 (279 MM) MINIMUM MEASURED HORIZONTALLY BETWEEN THE
 VERTICAL PLANES OF THE FOREMOST PROJECTION OF ADJACENT
 TREADS AND AT A RIGHT ANGLE TO THE TREAD?S NOSING.
  
 5) PLEASE SHOW THAT STAIR HAND RAILS ARE REQUIRED ON
 BOTH SIDES PER FBC 1011.11 HANDRAILS.
 FLIGHTS OF STAIRWAYS SHALL HAVE HANDRAILS ON EACH SIDE
 AND SHALL COMPLY WITH SECTION 1014.
  
 6) PLEASE SHOW THE STAIR LANDINGS SIZES PER FBC 1011.6
  
 7) PLEASE SHOW THE STAIR AND RAMP WIDTHS FBC 1005 - -
 FBC 1012.5.1
  
 8) PLEASE SHOW THAT HAND RAILS ARE REQUIRED ON BOTH
 SIDES OF THE RAMP - FBC 1012.8 HANDRAILS.
 RAMPS WITH A RISE GREATER THAN 6 INCHES (152 MM) SHALL
 HAVE HANDRAILS ON BOTH SIDES.
  
 9) PLEASE SHOW THE RAMP LANDING SIZES - FBC A
  
 10) PLEASE SHOW THE RAMP SLOPE - FBC A
  
 11) PLEASE SHOW THE RAMP HAND RAIL HEIGHT - FBC A
  
 12) PLEASE SHOW THE ACCESSIBLE DOOR WIDTHS - FBC A
  
 13) BUILDING ADDRESS APPEARS TO BE INCORRECT ON THE
 BUILDING PERMIT APPLICATION AND THE DRAWINGS - PLEASE
 CORRECT.
  
 14) PLEASE SHOW THE ACCESSIBLE RESTROOM DIMENSION
 DETAILS FOR THE GRAB BAR SIZES AND LOCATIONS, MIRROR,
 TOILET PAPER HOLDER, FIXTURE CLEAR FLOOR SPACE ETC PER
 FBC A CHAPTER 6
  
 15) PLEASE SHOW THE ACCESSIBLE ROUTE TO UNIT 100A - FBC
 A 206.4 ENTRANCES.
 ENTRANCES SHALL BE PROVIDED IN ACCORDANCE WITH 206.4.
 ENTRANCE DOORS, DOORWAYS, AND GATES SHALL COMPLY WITH
 404 AND SHALL BE ON AN ACCESSIBLE ROUTE COMPLYING WITH
 402.
  
 16) DRAWING S0.01 SHOWS WIND SPEED USED FOR WIND DESIGN
 AS 169MPH - WIND DESIGN SPEED SHOULD BE 170MPH PER FBC
 WPB SECTION 120
  
 17) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR STOREFRONT WINDOWS
 AND DOORS - ALL PRODUCT APPROVALS NEED TO BE REVIEWED
 AND MARKED APPROVED BY THE DESIGNER OF RECORD FBC WPB
 107.3.4
  
 18) CANNOT REUSE STOREFRONT WINDOWS UNLESS YOU HAVE A
 CURRENT PRODUCT APPROVAL FOR THEM - FBC EXISTING 707.4
 REPLACEMENT OF WINDOWS AND DOORS.
 THE REPLACEMENT OF GARAGE DOORS, EXTERIOR DOORS,
 SKYLIGHTS, AND OPERATIVE AND INOPERATIVE WINDOWS SHALL
 BE DESIGNED AND CONSTRUCTED TO COMPLY WITH CHAPTER 16
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 19) NFIP - JOB IS A SUBSTANTIAL IMPROVEMENT JOB VALUE +
 5 YEAR ACCUMULATION = 1,015,272.00 - BUILDING VALUE =
 1,355,080.00 - THE BUILDING LOWEST FLOOR ELEVATION
 NEEDS TO BE AT 14.10 NAVD - PLEASE PROVIDE AN ELEVATION
 CERTIFICATE TO VERIFY THE LOWEST FLOOR ELEVATION -
 ORDINANCE NO. 4729-17 SEC. 18-35 (A) AND (B)