Plan Review Notes For Permit 22030285 |
Permit Number |
22030285 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-04-26 10:14:18 | 1ST PLUMBING REVIEW | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. PAGE P2.1 - V7 FPC 410.3 - A HIGH/LOW DRINKING | | FOUNTAIN IS REQUIRED. | | | | 2. PAGE P0.1 - 2020 FPC - 607.1.1 TEMPERATURE LIMITING | | MEANS ? THE THERMOSTAT CONTROL ON THE WATER HEATER | | CANNOT BE THE LIMITING DEVICE FOR HOT WATER DELIVERY. | | PLEASE PROVIDE A DETAIL FOR A LIMITING DEVICE FOR THE | | PURPOSE OF HOT WATER DELIVERY. THIS WOULD BE IN | | ADDITION TO THE REQUIREMENTS FOR TEMPERED WATER FOR | | PUBLIC HAND-WASHING 607.1.2/419.5. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | |
|