2022-05-02 17:12:351ST REVIEW FMC
 PERMIT: 22030285
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FEC 101.5.1.1.2
  
 2) PLEASE SHOW THAT THE CONDENSING UNITS ARE A MINIMUM
 OF 10 FEET FROM THE ROOF EDGE OR PROVIDE GUARDS. FMC
 304.11
  
 3) PLEASE SHOW THE ROOF ACCESS. FMC 306.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  