2022-05-02 17:12:35 | 1ST REVIEW FMC | | PERMIT: 22030285 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | CALCULATIONS. FEC 101.5.1.1.2 | | | | 2) PLEASE SHOW THAT THE CONDENSING UNITS ARE A MINIMUM | | OF 10 FEET FROM THE ROOF EDGE OR PROVIDE GUARDS. FMC | | 304.11 | | | | 3) PLEASE SHOW THE ROOF ACCESS. FMC 306.5 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|