Plan Review Notes
Plan Review Notes For Permit 22030285
Permit Number 22030285
Review Stop B
Sequence Number 1
Notes
Date Text
2022-05-04 11:11:56WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22030285
 ADD: 1400 ELIZABETH AVE.
 CONT: TBD/ TO BE DETERMINED
 TEL: ???
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 04TH/ 2022
 ACTION: DENIED
  
 1) PLEASE BE AWARE THIS BUILDING IS LOCATED IN A AE
 FLOOD ZONE. THE BASE FLOOD ELEVATION IS (BFE 12.1 FEET
 NAVD88). THE BUILDING WAS BUILT IN 1950 MAKING THE
 BUILDING A PRE-FIRM BUILDING. THE PALM BEACH COUNTY
 PROPERTY APPRAISERS OFFICE (2021 TAX YEAR) LIST THE
 TOTAL MARKET VALUE OF $506,387.00 DOLLARS, LAND AT
 $174,168.00 DOLLARS AND IMPROVEMENT VALUE OF $332,210
 DOLLARS OF VALUE. THE DOLLAR AMOUNT FOR THIS PERMIT
 VALUE IS $500,000.00 DOLLARS IN VALUE MAKING THIS A
 SUBSTANTIAL IMPROVEMENT.
  
 WEST PALM BEACH MUNI CODE. SUBSTANIAL IMPROVEMENT.
 SECTION 94-546 PROVISIONS FOR FLOOD HAZARD REDUCTION.
 (A)(3) ANY ALTERATION, REPAIR, RECONSTRUCTION, OR
 IMPROVEMENTS TO A PROPERTY WHICH THE CUMULATIVE COST
 FOR ANY FIVE YEAR PERIOD EQUALS OR EXCEEDS 50 % OF THE
 BUILDING VALUE AT THE COMMENCEMENT OF THE FIVE YEAR
 PERIOD SHALL MEET THE REQUIREMENTS OF NEW CONSTRUCTION
 AS CONTAINED IN THIS ARTICLE.
 YOU MAY WAN TO REVIEW FEMA PUBLICATION FEMA P-758
 SUBSTANTIAL IMPROVEMENT/ SUBSTANTIAL DAMAGE DESK
 REFERENCE, AND REVIEW PAGE 6-9.
 YOU MAY ALSO WANT TO GET A CERTIFIED APPRAISER DONE OF
 THE BUILDING (IMPROVED VALUE) TO SEE IF THIS
 RENOVATION/ REMODEL WOULD NO LONGER CLASSIFY AS A
 SUBSTANTIAL IMPROVEMENT. THE OTHER ISSUE THAT MAY OCCUR
 IS THE OLD DOCKING STATION WITHIN THE BUILDING AND
 LOWER FLOOR LEVEL. YOU WILL NEED TO ESTABLISH THE FLOOR
 ELEVATIONS HIGH AND LOWER FLOOR LEVELS IN NAVD 88. ANY
 ATTENDANT UTILITIES INCLUDING A/C COMPRESSORS AND OR
 ELECTRICAL GENERATORS WILL ALSO BE SHOWN ON THE SURVEY.
 DEPENDING ON THE OUTCOME OF THE SURVEY ANOTHER FEMA
 PUBLICATION TECHNICAL BULLETIN TB 3-93 FOR
 NON-RESIDENTIAL FLOOD PROOFING REQUIREMENTS &
 CERTIFICATION.
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1
 BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS. ( 8) FLOOD REQUIREMENTS ELEVATIONS,
 ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS.
  
 (2) ONCE THE FIRST-FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED. W. P. B.
 ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2
 FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON
 PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND
 PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION
 CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL.
  
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS. W.
 P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS
 (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS
 COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR
 ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL
 INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR
 ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING
 JURISDICTION.
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
 2020 FBC-BUILDING SECTION 1612 FLOOD ZONES, AND ASCE 24
 MANUAL.
  
 2) SHEET A0.01:
  
 2A) PLEASE PROVIDE A SURVEY OF THE PROPERTY THE
 PROPERTY APPRAISERS OFFICE PICTURE OF BUILDING PROPERTY
 LINES DOES NOT SHOW A OFFSET IN THE RIGHT SIDE OF THE
 BUILDINGS. BUILDINGS CAN NOT TRANSGRESS PROPERTY LINES.
 2020 W. P. B. ADMINISTRATIVE CODE107.3.5 MINIMUM PLAN
 REVIEW CRITERIA SURVEY.
  
 2B) THE FRONT OF THE BUILDING THERE ARE IS A STAIR
 ENTRY, WITHIN THE BUILDING LOWER FLOOR LEVEL STAIRS AND
 THE REAR OF THE BUILDING AGAIN THE REAR EXIT STAIRS.
 PLEASE SHOW COMPLIANCE WITH 2020 FBC-ACCESSIBILITY CODE
 SECTION 201.1.1 VERTICAL ACCESSIBILITY.
 202.4.1. DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COST ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COST ASSOCIATED WITH RELOCATING AN ACCESSIBLE DRINKING
 FOUNTAIN.
  
 202.4.2 ACCESSIBILITY FEATURES IN THE EVENT OF
 DISPROPORTIONALITY ($500,000.00 X 0.20= $100,000.00
 DOLLARS). WHEN THE COST OF THE ALTERATIONS NECESSARY TO
 MAKE THE PATH OF TRAVEL TO THE ALTERED AREAS FULLY
 ACCESSIBLE IS DISPROPORTIONATE TO THE COST OF THE
 OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE MADE
 ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE ACCESSIBLE
 WITHOUT INCURRING DISPROPORTIONATE COST. IN CHOOSING
 WHICH ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO
 THOSE ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS,
 IN THE FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE;
 (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT
 LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM; (IV) ACCESSIBLE TELEPHONES: (V)
 ACCESSIBLE DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE,
 ADDITIONAL ACCESSIBLE ELEMENTS SUCH AS PARKING,
 STORAGE, AND ALARMS.
  
 2C) THE BREAK ROOM SINK DOES NOT INDICATE IF THIS IS
 GOING TO BE A FRONT APPROACH OR SIDE APPROACH, NOT
 SHOWN ON THE PLANS. 2020 FBC-ACCESSIBILITY CODE 606.2
 CLEAR FLOOR SPACE.
  
 2D) THE FLOOR PLAN SHOWS TABLE AND CHAIRS IN THE BREAK
 ROOM BUT NOT COMPLIANCE WITH 2020 FBC-ACCESSIBILITY
 CODE SECTION 226.1 WHERE DINING SURFACES ARE PROVIDED
 FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST 5
 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 2E) 2020 FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF
 DINING SURFACES AND WORK SURFACES SHALL BE 28 INCHES
 MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 2F) 2020 FBC-ACCESS. CODE 226.2 DISPERSION. DINING
 SURFACES AND WORK SURFACES REQUIRED TO COMPLY WITH 902
 SHALL BE DISPERSED THROUGHOUT THE SPACE OR FACILITY
 CONTAINING DINING SURFACES AND WORK SURFACES.
  
 2G) IT APPEARS THERE MAYBE A SINGLE WATER FOUNTAIN IN
 FRONT OF THE RESTROOMS, IN THE CORRIDOR. SHEET A1.01
 SHOWS A DETAIL MARKER DETAIL 8/ A6.01 WHICH IS FOR
 STADIUM SEATING? DISCREPANCY IN PLANS. 2020
 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM NUMBER. NO FEWER
 THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6
 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7.
  
 3) SHEET A1.01:
 3A) SHEET A1.01 SHOW DETAIL 5/ A6.01 FOR GUARDRAIL AT
 LOWER FLOOR LEVEL, BUT AGAIN WRONG DETAIL DETAIL 5 IS
 FOR RESTROOM ELEVATION. DISCREPANCY IN PLANS. NOTE
 THERE ARE NO DETAILS OF FRONT AND REAR STAIRS, GUARD/
 HAND RAILS. 107.2.1.2. DRAWINGS & SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC TO THE TECHNICAL CODES.
 CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 4) SHEET M3.1 SHOWS THE INSTALLATION OF ROOF TOP
 CONDENSERS BUT NO ACCESS TO THE ROOF IS SHOWN ON EITHER
 THE LIFE SAFETY PLAN NOR A1.01. 2020 FBC-M 306.5
 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES.
 WHERE EQUIPMENT REQUIRING ACCESS OR APPLIANCES ARE
 LOCATED ON AN ELEVATED STRUCTURE OR THE ROOF OF A
 BUILDING SUCH THAT PERSONNEL WILL HAVE TO CLIMB HIGHER
 THAN 16 FEET ABOVE GRADE TO ACCESS SUCH EQUIPMENT OR
 APPLIANCES, AN INTERIOR OR EXTERIOR MEANS OF ACCESS
 SHALL BE PROVIDED. SUCH ACCESS SHALL NOT REQUIRE
 CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 INCHES IN
 HEIGHT OR WALKING ON ROOFS HAVING A SLOPE GREATER THAN
 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT
 SLOPE). SUCH ACCESS SHALL NOT REQUIRE THE USE OF
 PORTABLE LADDERS. WHERE ACCESS INVOLVES CLIMBING OVER
 PARAPET WALLS, THE HEIGHT SHALL BE MEASURED TO THE TOP
 OF THE PARAPET WALL.
  
 5) SHEET M7.1 SHOWS ROOF TOP PRE-ENGINEERED ROOF
 STANDS, MISSING THE PRODUCT APPROVAL FOR ROOF STANDS.
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31)(G) PRE-ENGINEERED A/C STANDS
  
 6) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 7) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  