Plan Review Notes For Permit 22030266
Permit Number 22030266
Review Stop M
Sequence Number 1
Notes
Date Text
2022-04-11 10:19:391ST REVIEW FMC
 PERMIT: 22030266
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ENERGY CALCULATIONS: PAGE 19 OF 27 CALLS OUT THE
 AREA FOR AHU-1 AS 913 SQ.FT. AND THE AREA FOR THE RTU-1
 IS 1460. PAGE 1 OF 2 FOR THE MECHANICAL EQUIPMENT
 SIZING CALCULATIONS CALLS OUT 1318 SQ. FT. FOR THE
 AHU-1 AND PAGE 2 OF 2 CALLS OUT 1460 SQ. FT. OF AREA
 FOR THE RTU-1. PLEASE CORRECT THIS AS EACH SHOULD BE
 BASED ON THE SAME SQ. FT. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  