2022-04-18 14:45:561ST GAS REVIEW
  
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - COULD YOU PLEASE SUBMIT A
 FLOOR PLAN VIEW WITH THE LOCATION OF THE GAS TO
 INDICATE:
  
 A. WHERE THE SLEEVING WILL BE TERMINATED TO SHOW
 COMPLIANCE WITH G2415.14 (404.14).
  
  
 2. 2017 WPB AMENDS 107.2.1 - IN REGARDS TO THE P.E.
 (PLASTIC) PIPE, PLEASE SHOW THE ROUTING ON THE FLOOR
 PLAN TO SHOW COMPLIANCE WITH G2415.17.1 (404.17.1), AS
 PLASTIC PIPE IS NOT ALLOWED WITHIN OR UNDER ANY
 BUILDING OR SLAB.
  
 3. 2017 WPB AMENDS 107.2.1 - PLEASE HAVE THE PERSON WHO
 IS RESPONSIBLE FOR THE DRAWING SIGN THE DRAWINGS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  