2022-05-31 17:11:22EXTERIOR COOLER
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) WIND DESIGN ON THE COOLER TIE DOWN CALCULATIONS AND
 THE DRAWINGS SHOW - RISK CAT. II WITH WIND SPEED OF
 169MPH - FOR A RISK CAT. II THE WIND SPEED SHOULD BE
 170MPH PER FBC WPB SECTION 120.