2022-03-29 15:01:36ELECTRIC REVIEW FAILED
 1)ELECTRICAL RISER DIGRAM DETAILS 2/0 CONDUCTORS
 FEEDING 200 AMP PANEL. THE AMPACITY OF THESE CONDUCTORS
 MAY NOT BE ADUSTED AS THEY DO NOT CARRY THE ENTIRE LOAD
 ASSOCIATED WITH THE DWELLING UNIT AS REQUIRED PER NEC,
 SEE BELOW..
  
 310.15 (B)(7)(1) FOR A SERVICE RATED 100 THROUGH 400
 AMPERES, THE SERVICE
 CONDUCTORS SUPPLYING THE "ENTIRE" LOAD ASSOCIATED WITH
 A
 ONE-FAMILY DWELLING, OR THE SERVICE CONDUCTORS
 SUPPLYING
 THE "ENTIRE" LOAD ASSOCIATED WITH AN INDIVIDUAL
 DWELLING UNIT
 IN A TWO-FAMILY OR MULTIFAMILY DWELLING, SHALL BE
 PERMITTED
 TO HAVE AN AMPACITY NOT LESS THAN 83 PERCENT OF THE
 SERVICE
 RATING.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved