Plan Review Notes For Permit 22030135 |
Permit Number |
22030135 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-05-06 07:20:07 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 2- 1 HP MOTORS PER 430.248 DRAW 10 AMPERES EACH, HOW | | DOES THIS FIT ON A 20 AMPERE CIRCUIT? 430.22, 430.52, | | 430.248 |
|