2022-03-03 12:38:49THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION ON THE SITE PLAN WITH A
 STAGE.
  
 HOW ARE THIS STAGES CONSTRUCTED, THE HEIGHT FROM THE
 GROUND, ANY RAILINGS OR STAIRS, STAIR(S) LOCATION(S),
 AND WILL POWER BE SUPPLED TO THE STAGE AND HOW?
  
 PLEASE PROVIDE SPECIFIC DETAILS.
  
  
 2) THERE DOES NOT APPEAR TO BE INDICATIONS OF A FENCE
 NOR GATES ON THE SITE PLAN.
  
 PLEASE CONFIRM IF THIS IS CORRECT AND PROVIDE THE SIZE
 & TYPE OF ANY PROPOSED FENCE AND SIZE OF GATE OPENINGS
 AND IF THE GATES HAVE LATCHES.
  
 ANY GATE SHALL NOT BE LOCKED AGAINST EGRESS,
  
  
 3) THERE ARE INDICATIONS OF CHAIRS IN A SEMI-CIRCLE.
  
 PLEASE PROVIDE THE TYPE OF CHAIRS, IF THEY ARE
 INTERLOCKING OR STAND ALONE, THE TOTAL NUMBER OF
 CHAIRS, NUMBER OF CHAIRS IN EACH ROW, WIDTH BETWEEN
 CHAIRS AND WIDTH OF EACH ISLES.
  
  
 4) THERE SHALL BE NO OEPN FLAMES OR PYROTECHNICS
 ASSOCIATED WITH THIS EVENT WITHOUT A WRITTEN
 APPLICATION AND APPROVAL THROUGH THE OFFICE OF THE FIRE
 MARSHAL.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  