2022-03-03 12:38:49 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE IS AN INDICATION ON THE SITE PLAN WITH A |
| STAGE. |
| |
| HOW ARE THIS STAGES CONSTRUCTED, THE HEIGHT FROM THE |
| GROUND, ANY RAILINGS OR STAIRS, STAIR(S) LOCATION(S), |
| AND WILL POWER BE SUPPLED TO THE STAGE AND HOW? |
| |
| PLEASE PROVIDE SPECIFIC DETAILS. |
| |
| |
| 2) THERE DOES NOT APPEAR TO BE INDICATIONS OF A FENCE |
| NOR GATES ON THE SITE PLAN. |
| |
| PLEASE CONFIRM IF THIS IS CORRECT AND PROVIDE THE SIZE |
| & TYPE OF ANY PROPOSED FENCE AND SIZE OF GATE OPENINGS |
| AND IF THE GATES HAVE LATCHES. |
| |
| ANY GATE SHALL NOT BE LOCKED AGAINST EGRESS, |
| |
| |
| 3) THERE ARE INDICATIONS OF CHAIRS IN A SEMI-CIRCLE. |
| |
| PLEASE PROVIDE THE TYPE OF CHAIRS, IF THEY ARE |
| INTERLOCKING OR STAND ALONE, THE TOTAL NUMBER OF |
| CHAIRS, NUMBER OF CHAIRS IN EACH ROW, WIDTH BETWEEN |
| CHAIRS AND WIDTH OF EACH ISLES. |
| |
| |
| 4) THERE SHALL BE NO OEPN FLAMES OR PYROTECHNICS |
| ASSOCIATED WITH THIS EVENT WITHOUT A WRITTEN |
| APPLICATION AND APPROVAL THROUGH THE OFFICE OF THE FIRE |
| MARSHAL. |
| |
| PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT. |
| |
| |
| |
| 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |