2022-03-09 11:16:08 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE IS AN INDICATION ON THE DEMO PLAN: "REMOVE |
| EXISTING FLOORING AND BASEBOARDS THROUGHOUT", HOWEVER, |
| THERE IS NO INDICATION OF THE REPLACEMENT FLOOR |
| PRODUCT/MATERIAL. |
| |
| THERE IS ALSO A SPEC SHEET FOR THE FLOOR UNDERLAYMENT, |
| BUT NO SPEC SHEET NOR A PRODUCT NAME FOR THE ACTUAL |
| PROPOSED REPLACEMENT FLOORING. |
| |
| VINYL FLOORING IS MANUFACTURED AROUND THE WORLD AND NOT |
| ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS. |
| |
| PER NFPA 101, CH 30 |
| |
| 30.3.3.3 INTERIOR FLOOR FINISH. |
| 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| ACCORDANCE WITH |
| SECTION 10.2. |
| |
| 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| 10.2.2.2 |
| ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| HAVE A |
| MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| |
| FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING |
| PRODUCT NAME AND THE PRODUCT SPEC SHEETS OF THE |
| PROPOSED FINISHED |
| FLOORING INDICATING THE FIRE BEHAVIOR RATING. |
| |
| IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, |
| NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS |
| WOULD NOT BE REQUIRED. |
| |
| PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL |
| FLOORING, WOOD/VINYL LAMINATES, ETC. |
| |
| |
| 2) THE ARE INDICATIONS OF DEMO WORK. |
| |
| FIRE SPRINKLERS AND FIRE ALARM EQUIPMENT SHALL BE |
| PROTECTED FROM PAINTING OR DAMAGE. |
| |
| THE FIRE SPRINKLER/FIRE ALARM SYSTEMS SHALL BE |
| MAINTAINED THROUGHOUT DEMO AND RECONSTRUCTION. |
| |
| PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND ENSURE |
| COMPLIANCE. |
| |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |