Plan Review Notes
Plan Review Notes For Permit 22030035
Permit Number 22030035
Review Stop G
Sequence Number 2
Notes
Date Text
2022-04-14 09:16:342ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 22030035
 4/14/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENT #2 FROM THE 1ST
 REVIEW COPIED BELOW STILL EXISTS. PLEASE COMPLY.
  
 2) FAILED. SHEETS P3.1 & P6.1: REFER TO TABLE 402.4(5)
 FBC FG- THE MAIN SUPPLY PIPE FROM THE METER TO THE 1ST
 TEE SHALL BE MINIMUM 1-1/2 FOR THE TOTAL BTU LOAD OF
 3,249,000 AT A DEVELOPED SYSTEM LENGTH OF 141 FT.- SEC.
 402.4.1 FBC FG. THE 1-1/2 MAIN SUPPLY PIPE FROM THE
 METER TO THE 1ST TEE IS NOT INDICATED, AND THE 3/4-INCH
 PIPE FROM THE TEE TO THE LOW PRESSURE REGULATOR IS
 UNDERSIZED. A MINIMUM 1-1/4-INCH PIPE IS REQUIRED- SEE
 TABLE 402.4(5) FBC FG.
  
 2A) THE 23 FT. BRANCHES TO THE WATER HEATERS SHALL BE
 SIZED AT MINIMUM 1-INCH PER TABLE 402.4(2).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  