Notes |
Date |
Text |
2022-04-14 09:16:34 | 2ND REVIEW FBC-2020 FUEL GAS | | PERMIT- 22030035 | | 4/14/2022 | | | | CODES IN EFFECT: | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. COMMENT #2 FROM THE 1ST | | REVIEW COPIED BELOW STILL EXISTS. PLEASE COMPLY. | | | | 2) FAILED. SHEETS P3.1 & P6.1: REFER TO TABLE 402.4(5) | | FBC FG- THE MAIN SUPPLY PIPE FROM THE METER TO THE 1ST | | TEE SHALL BE MINIMUM 1-1/2 FOR THE TOTAL BTU LOAD OF | | 3,249,000 AT A DEVELOPED SYSTEM LENGTH OF 141 FT.- SEC. | | 402.4.1 FBC FG. THE 1-1/2 MAIN SUPPLY PIPE FROM THE | | METER TO THE 1ST TEE IS NOT INDICATED, AND THE 3/4-INCH | | PIPE FROM THE TEE TO THE LOW PRESSURE REGULATOR IS | | UNDERSIZED. A MINIMUM 1-1/4-INCH PIPE IS REQUIRED- SEE | | TABLE 402.4(5) FBC FG. | | | | 2A) THE 23 FT. BRANCHES TO THE WATER HEATERS SHALL BE | | SIZED AT MINIMUM 1-INCH PER TABLE 402.4(2). | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|