Plan Review Notes
Plan Review Notes For Permit 22030035
Permit Number 22030035
Review Stop G
Sequence Number 1
Notes
Date Text
2022-03-09 08:33:481ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22030035
 3/9/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P6.1: REVISE THE 2 PSI SYSTEM TOTAL LOAD OF
 1,776,000 BTU TO INCLUDE THE 1,473,000 BTU LOAD OF THE
 GENERATOR- SEC. 402.2 FBC FG.
  
 2) SHEETS P3.1 & P6.1: REFER TO TABLE 492.4(5) FBC FG-
 THE MAIN SUPPLY PIPE FROM THE METER TO THE 1ST TEE
 SHALL BE MINIMUM 1-1/2 FOR THE TOTAL BTU LOAD OF
 3,249,000 AT A DEVELOPED SYSTEM LENGTH OF 141 FT.- SEC.
 402.4.1 FBC FG.
  
 3) P3.1 & P6.1: IT APPEARS THAT THE NEW GAS PIPE TO THE
 GENERATOR WILL BE RUN UNDERGROUND. PLEASE SPECIFY THE
 TYPE OF PIPING AND PROVIDE THE PIPE SIZING TABLE USED-
 SECS. 402.3 & 403.1 FBC FG.
  
 4) P3.1 & P6.1: PLEASE PLACE A NOTE TO INDICATE THE
 GENERATOR INSTALLATION SHALL BE DONE UNDER A SEPARATE
 PERMIT- SECS. 105.1 & 107.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  