Plan Review Notes For Permit 22030015 |
Permit Number |
22030015 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-03-10 16:00:28 | PLEASE SUBMIT MIT A NEW REVISION FORM WITH THE | | DESCRIPTION TYPED OR PRINTED, THIS REVIEWER CANNOT MAKE | | OUT THE LAST WORD IN THE DESCRIPTION. IT APPEARS TO | | READ- REMOVE DUCT DETECTOR FROM AIR CONDITION DETECTOR? | | WHY ARE YOU REMOVING THE DUCT DETECTOR FROM THE RTU'S? | | PLEASE PROVIDE PROOF THAT THE DUCT DETECTORS ARE NOT | | REQUIRED. FBC 107.2.1 | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | | | | | |
|