2022-03-01 10:26:29 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected]. |
| |
| 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| FL16709-R9 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-4 TO |
| INCLUDE LIMITATIONS PAGE(S). THE EVALUATION REPORTS CAN |
| BE PRINTED FROM THE SUMMARY OF PRODUCTS LOCATED AT THE |
| BOTTOM OF THE COVER PAGE. PRINT PAGES 1-4 ONLY. |
| 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL16709-R9 SELECTED OPTION FOR SYSTEM NO W-5; |
| EXPOSURE (C); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H<15); |
| ULTIMATE WIND SPEED (180) IS NOT CORRECT. THE CORRECT |
| EXPOSURE FOR THE LISTED ADDRESS IS EXPOSURE D, CORRECT |
| WIND SPEED IS (170). PRODUCT APPROVAL FL16709-R9 WILL |
| NOT SATISFY EXPOSURE CATEGORY D ENCLOSED AREAS WITHOUT |
| USING INSULATION OR PROVIDING ENGINEERED ENHANCED |
| NAILING. PROVIDE. |
| 3. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| APPROVALS/NOA'S FOR THE PROPOSED ASPHALT SHINGLE |
| ROOFING SYSTEM TO BE USED. INCLUDE COVER PAGE, |
| EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS FOR |
| SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS |
| MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL |
| DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY |
| COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC |
| ENGINEERING. |
| 4. FBC R 905.1.1 ASPHALT SHINGLE, METAL, MINERAL |
| SURFACE, SLATE AND SLATE-TYPE ROOFING MUST COMPLY WITH |
| NEW 2020 BUILDING CODE UNDERLAYMENT REQUIREMENTS. |
| PROVIDE METHOD OF COMPLIANCE. (IF USING DOUBLE 30# FELT |
| INDICATE ON ROOF DRAWING/SKETCH). |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| |