Plan Review Notes
Plan Review Notes For Permit 22021370
Permit Number 22021370
Review Stop E
Sequence Number 1
Notes
Date Text
2022-03-26 11:49:06ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. A COMPREHENSIVE PLAN REVIEW COULD NOT BE COMPLETED
 AT THIS TIME. NO ELECTRICAL PLAN HAS BEEN SUBMITTED,
 ONLY SPECIFICATIONS FROM MANUFACTURER. PLEASE PROVIDE
 ELECTRICAL PLAN SIGNED BY ELECTRICAL CONTRACTOR
 QUALIFIER, OR SIGNED/SEALED BY DESIGN PROFESSIONAL. TO
 INCLUDE WIRE SIZES, ANY REQUIRED DISCONNECTING MEANS
 FOR MOTORS, OVERCURRENT PROTECTION, AND LOAD
 CALCULATION AND ONE-LINE DIAGRAM OF EXISTING SERVICE TO
 INCLUDE BOTH NEW AND EXISTING LOADS.FBC 107.2.1 NEC 220
 FS 471.003(2)(H); 471.025; WPB FBC 107.1
  
 2. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF VACCUM
 SYSTEM SHOWING UL LISTING OR OTHER NRTL LISTING. NEC
 110.2 110.3B
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  