Date |
Text |
2022-03-26 11:49:06 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. A COMPREHENSIVE PLAN REVIEW COULD NOT BE COMPLETED |
| AT THIS TIME. NO ELECTRICAL PLAN HAS BEEN SUBMITTED, |
| ONLY SPECIFICATIONS FROM MANUFACTURER. PLEASE PROVIDE |
| ELECTRICAL PLAN SIGNED BY ELECTRICAL CONTRACTOR |
| QUALIFIER, OR SIGNED/SEALED BY DESIGN PROFESSIONAL. TO |
| INCLUDE WIRE SIZES, ANY REQUIRED DISCONNECTING MEANS |
| FOR MOTORS, OVERCURRENT PROTECTION, AND LOAD |
| CALCULATION AND ONE-LINE DIAGRAM OF EXISTING SERVICE TO |
| INCLUDE BOTH NEW AND EXISTING LOADS.FBC 107.2.1 NEC 220 |
| FS 471.003(2)(H); 471.025; WPB FBC 107.1 |
| |
| 2. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF VACCUM |
| SYSTEM SHOWING UL LISTING OR OTHER NRTL LISTING. NEC |
| 110.2 110.3B |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |