2022-04-29 09:39:43 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 22021356 |
| 4/29/22 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE A CLEAR SCOPE OF WORK FOR PLUMBING ON THE |
| PLAN. THE APPLICATION INDICATES REPLACEMENT OF THE |
| SHOWER HOWEVER IT APPEARS OTHER PLUMBING WORK MAY BE |
| PROPOSED. IDENTIFY THE LOCATION OF THE NEW SHOWER AND |
| INDICATE ALL COMPONENTS TO BE REPLACED- PAN, VALVE, |
| FAUCET, WALL AND FLOOR TILE AND SUBSTRATES. CLARIFY IF |
| THE EXISTING DRAIN LOCATION WILL BE REUSED OR |
| RELOCATED- SEC. 107.2.1 WPB. THE PLUMBING CONTRACTOR OF |
| RECORD SHALL PROVIDE HIS PRINTED NAME, LICENSE NUMBER, |
| AND SIGNATURE ON ALL PLUMBING PLANS HE/SHE DRAWS- SEC. |
| 107.2.1 WPB. |
| |
| 2) FAIR HOUSING DESIGN ACT COMPLIANCE. |
| WPB BUILDING DEPT. RECORDS INDICATE THE RESIDENTIAL |
| UNITS AT THE EDGE CONDOMINIUMS 300 S AUSTRALIAN AVE. |
| WERE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH THE |
| FAIR HOUSING DESIGN ACT. PLEASE NOTE THAT REPLACEMENT |
| OF FIXTURES SHALL BE EXACT SAME REPLACEMENTS IN SAME |
| LOCATIONS WITH THE SAME CLEARANCES AND MOUNTING HEIGHTS |
| AS THE ORIGINALS. ANY ALTERATIONS WILL REQUIRE A DESIGN |
| PROFESSIONAL TO SUBMIT DRAWINGS AND DETAILS IN |
| COMPLIANCE WITH THE FAIR HOUSING ACT GUIDELINES |
| CONTAINED IN THE FBC ACC AND/OR THE FAIR HOUSING DESIGN |
| ACT MANUAL- SEC. 107.2.1 WPB. |
| |
| PLEASE NOTE: AS AN ALTERNATIVE TO MEETING THE |
| GUIDELINES FOR THE BATH ALTERATIONS, THE OWNER AND |
| DESIGNER OF RECORD FOR THE PROPOSED PROJECT MAY PROVIDE |
| A SIGNED AND NOTARIZED AFFIDAVIT WHICH WOULD INDICATE |
| ACKNOWLEDGEMENT THAT THE PROPOSED DESIGN DOES NOT MEET |
| THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY |
| GUIDELINES, BUT WILL ALSO REQUIRE THE OWNER TO AGREE TO |
| REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF SALE IF |
| REQUESTED BY THE BUYER. IF THIS OPTION IS CHOSEN, |
| PLEASE SEND AN EMAIL TO [email protected] AND I WILL SEND A |
| COPY OF THE FAIR HOUSING AFFIDAVIT. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |