2022-04-20 12:57:51JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. FBC B 107.2.1. PLEASE PROVIDE ENGINEER'S SIGNED AND
 SEALED FASTENER SPACING DETAIL WITH CALCULATIONS FOR
 PERIMETERS AND CORNERS AS PER PRODUCT APPROVAL
 LIMITATIONS #7 OF MIAMI-DADE NOA NO.: 20-0131.01.
 PLEASE NOTE THIS PROJECT IS LOCATED IN AN EXPOSURE D
 CATEGORY AREA; ALSO NOTE: THERE IS NOT A SYSTEM WITHIN
 THIS PRODUCT APPROVAL THAT WILL MEET OR EXCEED EXPOSURE
 D ZONE 3 MINIMUM DESIGN PRESSURE REQUIREMENT OF -131.42
 WITHOUT ENGINEER?S SIGN AND SEALED ENHANCED NAILING
 CALCULATIONS. SECOND REQUEST.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  