Plan Review Notes For Permit 22021307 |
Permit Number |
22021307 |
|
Review Stop |
B |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2022-11-07 20:30:22 | 1. CONTRACTOR INFORMATION FOR MRH SUPPLIED TO ENGINEER | | FOR REQUIRED DESIGN PRESSURE CALCULATIONS APPEARS TO | | HAVE INADVERTENTLY BEEN SUBMITTED AS 48FT. PLEASE | | RESUBMIT CORRECT MRH TO ENGINEER FOR DESIGN PRESSURE | | CALCULATION BASED ON CORRECT DATA. FBC 107.2 | | 2. PLEASE PROVIDE A FLASHING DETAIL, OR ADD A NOTE TO | | THE PLAN, DEMONSTRATING COMPLIANCE WITH FBC R 703.4 OR | | FBC B 1405.4. | | |
|