Plan Review Notes
Plan Review Notes For Permit 22021250
Permit Number 22021250
Review Stop B
Sequence Number 3
Notes
Date Text
2022-07-26 10:09:42WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 22021250
 W. P. B. PERMIT: 21021446
 ADD: 3114 TUXEDO AVE.
 CONT: S. MACDONALD CONTRACTING
 TEL: 561-689-8848
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. JULY 26TH/2022
 ACTION: DENIED
  
 1) THE SHEET C-2 THE SITE PLAN & C3 ENLARGED SITE PLAN:
 1A) 2ND REQUEST. PLEASE NOTE THE SAME PLAN CAN BE USED
 BUT A SEPARATE PERMIT IS REQUIRED FOR STRIPING OF THE
 PARKING LOT. ALSO NOTE COMMENT 1B-1D WILL BE REVIEWED
 UNDER THE STRIPING PERMIT. FEES WILL NEED TO BE
 ADJUSTED SO SOME OF THE FUNDS GO TOWARDS THE EXTERIOR
 SITE WORK. PLEASE NOTE IF NO NEW PLANS ARE SUBMITTED
 FOR THE SITE WORK THEN THE CORRECTIONS WILL NEED TO
 SHOWN UNDER THE MASTER PERMIT/ REVISION. IF THE
 EXTERIOR SITE WORK IS TO BE SHOWN UNDER THIS REVISION,
 ON BOTH THE REVISION SHEET AND C1 COVER SHEET THE
 PROJECT DESCRIPTION WILL ALSO NEED TO BE UPDATED.
 CURRENTLY THE SCOPE OF WORK STATES INTERIOR BUILD-OUT
 OF EXISTING OPEN SPACE STRUCTURE, (PREVIOUSLY USE AS
 OFFICES).
  
 1ST ROUND COMMENT. A SEPARATE PERMIT IS REQUIRED FOR
 THE STRIPING OF THE PARKING LOT AND REQUIRED ACCESSIBLE
 PARKING SPACES AND ACCESS AISLES. 2020
 FBC-ACCESSIBILITY CODE SECTION ACCESSIBLE PARKING
 SPACES. 208.3. LOCATION.
 PARKING SPACES COMPLYING WITH 502 THAT SERVE A
 PARTICULAR BUILDING OR FACILITY SHALL BE LOCATED ON THE
 SHORTEST ACCESSIBLE ROUTE FROM PARKING TO AN ENTRANCE
 COMPLYING WITH 206.4.
  
 1B) 2ND REQUEST, SHOW THE ELEVATIONS AT THE CORNERS OF
 THE ACCESSIBLE PARKING SPACE AND ACCESS AISLE ( SHOW
 ELEVATION MARKERS) TO SEE IF THEY COMPLY WITH THE 2020
 ACCESSIBILITY CODE SECTION 502.4 ACCESS AISLE & PARKING
 SPACE SAME LEVEL/ 502.4, FLOOR AND GROUND SURFACES.
 PARKING SPACES AND THE ACCESS AISLES SERVING THEM SHALL
 COMPLY WITH 302. ACCESS AISLES SHALL BE AT THE SAME
 LEVEL AS THE PARKING SPACES THEY SERVE.
 CHANGES IN LEVEL ARE NOT PERMITTED. EXCEPTION: SLOPES
 NOT GREATER THAN 1:48 SHALL BE PERMITTED.
  
 1C) 2ND REQUEST SHOW ELEVATIONS WITH ELEVATION MARKERS.
 THERE IS NO DETAIL OF THE TRANSITION FROM THE SIDEWALK
 TO THE ACCESS AISLE SHOWING A DROPPED CURB.
 2020 FBC-ACCESSIBILITY CODE SECTION 406.5. LOCATION.
 CURB RAMPS AND THE FLARED SIDES OF THE CURB RAMPS SHALL
 NOT BE LOCATED SO THAT THEY DO NOT PROJECT INTO
 VEHICULAR TRAFFIC LANES, PARKING SPACES, OR PARKING
 ACCESS AISLES. CURB RAMPS AT MARKED CROSSINGS SHALL BE
 WHOLLY CONTAINS WITHIN THE MARKINGS, EXCLUDING FLARED
 SIDES. ALSO SEE FIGURE 406.4. LANDINGS AT THE TOP OF
 CURB RAMPS.
  
 1D) 2ND REQUEST. PLEASE SHOW HOW A CRUSHED AND
 COMPACTED SURFACE MEETS THE REQUIREMENTS OF 302 AND THE
 ADVISORY. THE ONLY TIME THIS HAS BEEN ALLOWED IS FOR
 TEMPORARY CONSTRUCTION TRAILERS.
 2020 FBC-ACCESSIBILITY CODE, ACCESSIBLE PARKING SPACES
 MUST MEET THE REQUIREMENTS OF 302.1 GROUND AND FLOOR
 SURFACES SHALL BE STABLE, FIRM, AND SLIP RESISTANT AND
 SHALL COMPLY WITH 302.
 ADVISORY 302.1. A STABLE SURFACE IS ONE THAT REMAINS
 UNCHANGED BY CONTAMINANTS OR APPLIED FORCES SO THAT
 WHEN THE CONTAMINANT OR FORCE IS REMOVED, THE SURFACE
 RETURNS TO ITS ORIGINAL CONDITION.
  
 1E) COMPLIED.
  
 2) THE LIFE SAFETY SHEET LS1:
 2A) SEMI-COMPLIED. SHEET LS1 & A8. THE REVISION NOW
 SHOWS COMPLIANCE FOR WHEELCHAIR ENTRY WITH SEAT BUT THE
 WATERCLOSET DOES NOT SHOW COMPLIANCE WITH THE REQUIRED
 SIDE GRAB BAR ACCESS. CODE 604.5.1.
  
 OLD 2ND ROUND COMMENTS. THE LS1 SHEET AND A8 SHOW A
 UNISEX ACCESSIBLE BATHROOM (SHOWER). THE SHOWER IS
 DEPICTED AS A 3X3 FOOT MODULAR PAN SHOWER. ON THE RIGHT
 SIDE OF THE SHOWER ENTRY IS AN EXTERIOR WALL. ON THE
 LEFT SIDE OF THE SHOWER THERE IS A WALL THAT PROJECTS
 OUT PAST THE SHOWER APPROXIMATELY 1 FOOT. THE 3 X3 FOOT
 SHOWER IS CONSIDERED A TRANSFER TYPE SHOWER SEE 608.2.1
 ACCESSIBILITY CODE AND REQUIRES AN ADDITIONAL ONE-FOOT
 CLEARANCE BEYOND THE SHOWER OPENING TO BE ABLE TO
 TRANSFER FROM A WHEELCHAIR WHEN PARALLEL WITH THE FRONT
 OF THE SHOWER. SEE FIGURE 608.2.1.
 2B) 2ND REQUEST. PLEASE REVIEW SHEET A8 DRINKING
 FOUNTAIN ELEVATION VIEWS. YES YOU MEET THE 27 MAX
 HEIGHT FOR THE LOWER DRINKING FOUNTAIN BUT NOT THE
 UPPER DRINKING FOUNTAIN AS DEPICTED SOME SORT OF
 BARRIER NEEDS TO BE PLACED FOR A BLIND PERSON WITH
 WALKING CANE IF WALKING TOWARDS THE UPPER DRINKING
 FOUNTAIN TO SHOW COMPLIANCE, SOME MANUFACTURES MAKE A
 SKIRT THAT CAN BE APPLIED TO THE UPPER FOUNTAIN FOR
 COMPLIANCE A OPTION.
 ORIGINAL COMMENT. THE LS1 SHEET AND A8 SHOW HIGH/ LOW
 DRINKING FOUNTAINS. DETAILS ON SHEET A8 SHOW A SIDE
 VIEW OF THE LOW SIDE DRINKING FOUNTAIN AT A HEIGHT OF 2
 FEET 3 INCHES FROM THE FLOOR LEVEL TO THE BOTTOM OF THE
 DRINKING FOUNTAIN IN COMPLIANCE WITH THE 2020
 ACCESSIBILITY CODE SECTION 307.2 PROTRUSION LIMITS. THE
 LEFT-HAND SIDE DRINKING FOUNTAIN MEETS THE REQUIREMENTS
 FOR STANDING OCCUPANTS BUT DOES NOT AS DEPICTED MEET
 THE PROTRUSION LIMITS, THE BOTTOM OF THE DRINKING
 FOUNTAIN IS HIGHER THAN 27 INCHES FROM THE FLOOR.
  
 2C-D) COMPLIED.
  
 3) 2ND REQUEST. SHEET A6.0:
 3A) 2ND REQUEST, NOT ADDRESSED. IF YOU CLASSIFY THE
 BUILDING AS A IIB THEN ALL FRAMING MEMBERS AND ROOF
 DECKING NEED TO BE IDENTIFIED TO MEET THAT DEFINITION
 FOUND UNDER TABLE 601 AND 603.1 OTHERWISE THE BUILDING
 SHOULD BE LABELED IIIB.
 ORIGINAL COMMENT. PLEASE NOTE THE COVERSHEET LIST THIS
 CONSTRUCTION TYPE AS IIB NON-SPRINKLERED BUILDING. THE
 BUILDING SECTIONS ON SHEET A6.0 DO NOT INDICATE IF THE
 TRUSSED ARCH IS STEEL OR LAMINATED WOOD? THE SECTION
 ALSO FAILED TO DEFINE THE ROOF FRAMING MEMBERS/ PURLINS
 AND THE ROOF SHEATHING MATERIAL? ADDITIONAL INFORMATION
 IS REQUIRED. 2020 FBC-BUILDING CODE 603.1 .1.3 ROOF
 CONSTRUCTION, INCLUDING GIRDERS, TRUSSES FRAMING AND
 DECKING. ALL MUST BE FIRE RETARDANT TREATED WOOD.
  
 3B) 2ND REQUEST, NOT ADDRESSED. PLEASE ADD RESPONSE
 NOTES TO PLAN INDICATING FLOOR LOADING. EVERY PERMIT
 STANDS ALONE FOR INFORMATION.
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 SECTION 2 & 3 BOTH SHOW A EXISTING CRAWL SPACE THE PLAN
 DOES NOT SHOW HOW THE ADDITIONAL GRAVITY LOADS PLUS
 STORAGE LOADS FROM THE NEW ATTIC SPACE ARE GOING TO BE
 TRANSFERRED TO THE FLOOR WITHOUT NEW COLUMNS OR PIERS
 BENEATH THE FIRST FLOOR LEVEL. 107.2. 1.. 2020 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION 107.2.1. DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 3C) 2ND REQUEST, NOT ADDRESSED. SORRY IT WAS ASSUMED
 THE MEZZANINE LEVEL (ATTIC) TO BE STORAGE. THE LS1
 SHEET NOR PROPOSED FLOOR PLAN SHOW A OCCUPANCY TYPE OR
 OCCUPANT LOAD. WITH THE 42 INCH HIGH RAIL WALL IT MEETS
 THE DEFINITION OF MEZZANINE, ASSUMED STORAGE SINCE
 THERE IS NO PERMANENT STAIR NOR IS THERE VERTICAL
 ACCESSIBILITY FOR OCCUPANT LOAD MORE THAN 5. SEE 2020
 FBC-ACCESSIBILITY 201.1.1 EXCEPTION 3 .
 ORIGINAL COMMENT. THE BUILDING SECTIONS SHOWN ON THIS
 SHEET DO NOT INDICATE WHAT TYPE OF LIVE LOADS ARE GOING
 TO BE PRODUCED BY STORAGE IN THE ATTIC. TABLE 1607.1
 STORAGE LIGHT IS 125 PSF, HEAVY AT 250 PSF
  
 3D) 2ND REQUEST, NOT ADDRESSED. 2020 FBC-BUILDING CODE
 SECTION 1603.1. THE DESIGN LOADS AND OTHER INFORMATION
 PERTINENT TO THE STRUCTURAL DESIGN SHALL BE INDICATED
 ON THE CONSTRUCTION DOCUMENTS.
  
 4) SHEET A8;
 4A-C) COMPLIED.
  
 4D) 2ND REQUEST.PLEASE PROVIDE SPECS FOR THE RAINBOW
 ATTIC STAIRS. 107.2.1 2020 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1. DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES.
  
 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  