2022-05-23 13:23:06 | 2ND REVIEW FBC-2020 PLUMBING |
| PERMIT- 22021250 |
| 3/7/2022 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES. |
| |
| 1) FAILED. SHEET LS1 & P3: PROVIDE PLUMBING FIXTURE |
| CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC P. |
| PLEASE NOTE THAT DRINKING FOUNTAINS AND SERVICE SINKS |
| ARE REQUIRED FIXTURES FOR BUSINESS OCCUPANCIES. PLEASE |
| REVISE THE PLANS ACCORDINGLY TO SHOW THE LOCATIONS OF |
| THE FIXTURES, PLUMBING PIPING AND ACCESSIBILITY |
| DETAILS- SEC. 107.2.1 WPB. FIXTURE CALCULATIONS NOT |
| PROVIDED. |
| |
| 3) FAILED. A1 & A8: MISSING ACCESSIBILITY DETAILS- FBC |
| ACC: THE CORRECTED PLANS STILL HAVE SOME MISSING |
| DETAILS. |
| |
| B) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR |
| THE LAVATORIES- SEC. 606.2. A 48-INCH DEPTH DIMENSION |
| IS REQUIRED. THE PLAN SHOWS 3'0". |
| E) FAILED. HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR |
| TO THE REFLECTIVE SURFACE- SEC. 603.3. THE DETAIL SHOWS |
| THE MEASUREMENT TO THE FRAME. DIMENSION NOT SHOWN TO |
| THE REFLECTIVE SURFACE. |
| F) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF |
| GRAB BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4, |
| FIGURES 604.5.1 & 604.5.2. THE DETAILS SHOW THE |
| MEASUREMENTS TO THE CENTERS OF THE BARS AND NOT TO THE |
| TOPS OF THE GRIPPING SURFACES. REAR WATER CLOSET GRAB |
| BAR DIMENSIONS NOT SHOWN. |
| H) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR |
| THE SHOWER- SECTION 608.2.1 REQUIRED CLEAR FLOOR SPACE |
| SHALL BE 30X48-INCHES IN A PARALLEL POSITIONED MEASURED |
| FROM THE CONTROL SIDE OF THE SHOWER. THE DRAWING SHOWS |
| THERE IS NOT ADEQUATE SPACE TO PROVIDED TO MEET |
| COMPLIANCE. |
| I) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF |
| GRAB BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3 AND |
| 608.3.1 NOT PROVIDED. |
| J) FAILED. LOCATION OF CONTROL, FAUCET, AND SHOWER |
| SPRAY IN THE SHOWER- SECTION 608.5.1. NOT PROVIDED. |
| L) FAILED. LOCATION OF ACCESSIBLE SHOWER SEAT- SECTIONS |
| 610.3 & 610.3.2. NOT PROVIDED. |
| M) FAILED. DRINKING FOUNTAINS: REFER TO SECS. 306, 307, |
| AND 602 AND PROVIDE DRINKING FOUNTAIN INSTALLATION |
| DETAILS AND ELEVATION VIEWS SHOWING KNEE AND TOE |
| CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. SHOW |
| THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A |
| FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SEC. |
| 602.2. SHOW THE LOCATIONS OF THE FOUNTAINS WILL BE IN |
| COMPLIANCE WITH SECTION 307.2 PROTRUSION LIMITS. THE |
| DRAWINGS SHOW THE DRINKING FOUNTAINS WILL BE PROTRUDING |
| INTO THE CIRCULATION PATH BEYOND THE MAXIMUM 4-INCHES |
| ALLOWED- SEC. 307.2 FBC ACC. WING WALLS ON EACH SIDE OF |
| THE FOUNTAIN CAN BE INSTALLED OR BARRIER-FREE TYPE |
| FOUNTAINS. |
| |
| NEW COMMENT: |
| |
| 1) SHEET A8: SHOW THE CENTERLINE OF THE TOILET PAPER |
| DISPENSER MEASURED FROM THE FRONT OF THE WATER CLOSETS |
| SEC. AND FIGURE 604.7 FBC ACC. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |