Plan Review Notes
Plan Review Notes For Permit 22021250
Permit Number 22021250
Review Stop P
Sequence Number 2
Notes
Date Text
2022-05-23 13:23:062ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22021250
 3/7/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES.
  
 1) FAILED. SHEET LS1 & P3: PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC P.
 PLEASE NOTE THAT DRINKING FOUNTAINS AND SERVICE SINKS
 ARE REQUIRED FIXTURES FOR BUSINESS OCCUPANCIES. PLEASE
 REVISE THE PLANS ACCORDINGLY TO SHOW THE LOCATIONS OF
 THE FIXTURES, PLUMBING PIPING AND ACCESSIBILITY
 DETAILS- SEC. 107.2.1 WPB. FIXTURE CALCULATIONS NOT
 PROVIDED.
  
 3) FAILED. A1 & A8: MISSING ACCESSIBILITY DETAILS- FBC
 ACC: THE CORRECTED PLANS STILL HAVE SOME MISSING
 DETAILS.
  
 B) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE LAVATORIES- SEC. 606.2. A 48-INCH DEPTH DIMENSION
 IS REQUIRED. THE PLAN SHOWS 3'0".
 E) FAILED. HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR
 TO THE REFLECTIVE SURFACE- SEC. 603.3. THE DETAIL SHOWS
 THE MEASUREMENT TO THE FRAME. DIMENSION NOT SHOWN TO
 THE REFLECTIVE SURFACE.
 F) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. THE DETAILS SHOW THE
 MEASUREMENTS TO THE CENTERS OF THE BARS AND NOT TO THE
 TOPS OF THE GRIPPING SURFACES. REAR WATER CLOSET GRAB
 BAR DIMENSIONS NOT SHOWN.
 H) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE SHOWER- SECTION 608.2.1 REQUIRED CLEAR FLOOR SPACE
 SHALL BE 30X48-INCHES IN A PARALLEL POSITIONED MEASURED
 FROM THE CONTROL SIDE OF THE SHOWER. THE DRAWING SHOWS
 THERE IS NOT ADEQUATE SPACE TO PROVIDED TO MEET
 COMPLIANCE.
 I) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3 AND
 608.3.1 NOT PROVIDED.
 J) FAILED. LOCATION OF CONTROL, FAUCET, AND SHOWER
 SPRAY IN THE SHOWER- SECTION 608.5.1. NOT PROVIDED.
 L) FAILED. LOCATION OF ACCESSIBLE SHOWER SEAT- SECTIONS
 610.3 & 610.3.2. NOT PROVIDED.
 M) FAILED. DRINKING FOUNTAINS: REFER TO SECS. 306, 307,
 AND 602 AND PROVIDE DRINKING FOUNTAIN INSTALLATION
 DETAILS AND ELEVATION VIEWS SHOWING KNEE AND TOE
 CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. SHOW
 THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A
 FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SEC.
 602.2. SHOW THE LOCATIONS OF THE FOUNTAINS WILL BE IN
 COMPLIANCE WITH SECTION 307.2 PROTRUSION LIMITS. THE
 DRAWINGS SHOW THE DRINKING FOUNTAINS WILL BE PROTRUDING
 INTO THE CIRCULATION PATH BEYOND THE MAXIMUM 4-INCHES
 ALLOWED- SEC. 307.2 FBC ACC. WING WALLS ON EACH SIDE OF
 THE FOUNTAIN CAN BE INSTALLED OR BARRIER-FREE TYPE
 FOUNTAINS.
  
 NEW COMMENT:
  
 1) SHEET A8: SHOW THE CENTERLINE OF THE TOILET PAPER
 DISPENSER MEASURED FROM THE FRONT OF THE WATER CLOSETS
 SEC. AND FIGURE 604.7 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  