Plan Review Notes For Permit 22021250 |
Permit Number |
22021250 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-03-10 16:27:54 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-22021250 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | | | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | CALCULATIONS. FBC EC C403.2.1 | | | | 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON | | FBC M 403.3.1.1 AND TABLE 403.3.1.1 USING THE CORRECT | | OCCUPANCY CLASSIFICATION FOR EACH USE OF SPACE IN THIS | | TENANT SPACE. | | | | 4) PLEASE SHOW THE CONDENSING PIPE MATERIAL, SIZE AND | | TERMINATION LOCATION. FBC M 307 | | | | 5) PLEASE PROVIDE A DETAIL OF THE WALLS TO CEILING FOR | | AHU?S 1 AND 2 AT THE FREE DRAW RETURNS. SHOW THE RETURN | | AIR PATH FROM THE ROOMS BACK TO THE AHU?S. FBC M 601.6 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|