Plan Review Notes For Permit 22021249 |
Permit Number |
22021249 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-02-25 13:31:06 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THERE IS AN INDICATION ON THE SITE PLAN OF THREE | | STAGES. | | | | HOW ARE THESE STAGES CONSTRUCTED, THE HEIGHT FROM THE | | GROUND, ANY RAILINGS OR STAIRS, STAIR(S) LOCATION(S), | | AND WILL POWER BE SUPPLED TO THE STAGE AND HOW? | | | | PLEASE PROVIDE SPECIFIC DETAILS. | | | | 2) THERE APPEARS BE BE INDICATIONS OF FENCES AND GATES | | ON THE SITE PLAN. | | | | PLEASE CONFIRM IF THIS IS CORRECT AND PROVIDE THE SIZE | | & TYPE OF FENCE AND SIZE OF GATE OPENING AND IF THE | | GATE HAS LATCHES. | | | | ANY GATE SHALL NO BE LOCKED AGAIST EGRESS, | | | | | | 3) THERE ARE NO INDICATIONS OF THE PROPOSED NUMBER OF | | PEOPLE IN ATTENDANCE. | | | | PLEASE PROVIDE THE PROPOSED COUNT AND HOW THIS COUNT | | WILL BE CONTROLLED SO AS TO NOT OVERCROWD THE EVENT. | | | | | | 4) THERE SHALL BE NO OEPN FLAMES OR PYROTECHNICS | | ASSOCIATED WITH THIS EVENT WITHOUT A WRITTEN | | APPLICATION AND APPROVAL THROUGH THE OFFICE OF THE FIRE | | MARSHAL. | | | | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT. | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|