Date |
Text |
2022-06-06 09:20:07 | CLIENT EMAILED PLANS WITH CORRECT SIGNATURE. I UPLOADED |
| THEM TO SIGNATURE FILE 6/6/22. MP |
2022-06-03 10:17:49 | SIGNATURE REVIEW FAILED |
| 1) PLANS TITELED PLAN EXIST, PLAN PROPOSED AND HVAC |
| APPEAR TO BE COPIES OF DIGITAL SIGNATURES OR DO NOT |
| HAVE THE REQUIED DIGITAL SIGNATURE. |
| |
| PLEASE FOLLOW THE DIRECTIONS OUTLINED BELOW TO CORRECT |
| THIS ISSUE.FS471/FS481 DOCUMENTS PREPARED BY AN |
| ARCHITECT OR ENGINEER AND SUBMITTED FOR PUBLIC RECORD |
| ARE TO BE SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY |
| SEALED AND SIGNED. |
| |
| EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN |
| TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF |
| APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX, |
| OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER |
| ORIGINAL WITH A WET SIGNATURE TO THE BUILDING |
| DEPARTMENT. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |
| SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO |
| BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED |
| DOCUMENTS ARE PREFERRED. |
| PLEASE EMAIL [email protected] AND CC TO |
| [email protected] WITH ANY QUESTIONS |
| |
| MICHAEL PETERSON |
| ELECTRICAL PLANS EXAMINER |
| [email protected] |
| 561-805-6746 |
| |
2022-05-26 11:12:40 | DIGITAL SIGNATURE ON THE MECHANICAL DRAWING IS A COPY |
| OF THE ORIGINAL DIGITAL SIGNATURE. PROVIDE THE |
| ORIGIANAL DIGITALLY SIGNED DRAWING. ME |