2022-02-25 15:47:08 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE IS AN INDICATION OF THE SCOPE OF WORK OF |
| REPLACING THE TILE AND THERE IS A SPEC SHEET FOR THE |
| FLOOR UNDERLAYMENT, BUT NO PRODUCT NAME NOR A PRODUCT |
| SPEC SHEET FOR THE ACTUAL PROPOSED TILE. |
| |
| FLOORING IS MANUFACTURED AROUND THE WORLD AND TILE CAN |
| HAVE DIFFERENT MEANING A PRODUCED DIFFERENTLY AND NOT |
| ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS. |
| |
| 30.3.3.3 INTERIOR FLOOR FINISH. |
| 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| ACCORDANCE WITH |
| SECTION 10.2. |
| |
| 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| 10.2.2.2 |
| ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| HAVE A |
| MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| |
| FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE PRODUCT |
| SPEC SHEETS OF THE PROPOSED FINISHED |
| TILEL FLOORING INDICATING THE FIRE BEHAVIOR RATING. |
| |
| *****FYI **** |
| |
| PLEASE PROVIDE THE TILE TYPE I.E. CERAMIC, MARBLE, |
| TERRACOTTA, STONE WHICH WOULD NOT REQUIRE A SPEC SHEET. |
| |
| FOR OTHER TYPE OF TILE PRODUCT TYPE I.E. VINYL OR VINYL |
| PLANKS, CORK, WOOD PLEASE PROVIDE THE MANUFACTURE |
| PRODUCT FLAME SPREAD/PRODUCT SAFETY TEST SHEET |
| |
| |
| |
| 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |