2022-03-12 16:09:41 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. INACCURATE LOAD CALCULATION PROVIDED. NO SMALL |
| APPLIANCE CIRCUITS SHOWN IN LOAD CALC, (MINIMUM OF 2 |
| REQUIRED) NEC 220 NEC 210.52B1, NEC 210.52B2 |
| |
| 2. PANEL SCHEDULE STATES |
| "DINING/LIVING/LIBRARY/HALLWAYS LIGHTS AND RECEPTACLES" |
| ALL ON 1 20 AMP CIRCUIT. THIS IS NOT PERMITTED SMALL |
| APPLIANCE CIRCUITS FEEDING DINING ROOMS SHALL SERVE NO |
| OTHER LOAD THAN RECEPTACLES. NO LIGHTING PERMITTED. NEC |
| 210.52B1 NEC 210.52B2 |
| |
| 3. RISER DIAGRAM SHOWS A EQUIPMENT GROUND FROM METER |
| CAN TO 1ST DISCONNECTING MEANS IN MAIN PANEL A. THIS IS |
| A PARRALLEL PATH GO THE GROUNDED CONDUCTOR AND IS NOT |
| PERMITTED. EQUIPMENT GROUND ORIGINATES ON THE LOAD SIDE |
| OF THE 1ST DISCONNECTING MEANS. PLEASE REMOVE NEC |
| 250.30A |
| |
| 4. TO MY KNOWLEDGE A 250AMP METER CAN DOES NOT EXIST. |
| THERE IS A 200AMP METERCAN AND A 320AMP CONTINUOUS |
| METERCAN (400 AMP). PLEASE SPECIFY THE CORRECT METER |
| CAN TO BE INSTALLED. NEC 110.3B FBC 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |