Plan Review Notes For Permit 22021184
Permit Number 22021184
Review Stop B
Sequence Number 1
Notes
Date Text
2022-03-02 12:10:45JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. FBC EB 706.1. NOT MORE THAN 25 PERCENT OF THE TOTAL
 ROOF AREA OR ROOF SECTION OF ANY EXISTING BUILDING OR
 STRUCTURE SHALL BE REPAIRED, REPLACED OR RECOVERED IN
 ANY 12-MONTH PERIOD UNLESS THE ENTIRE ROOFING SYSTEM OR
 ROOF SECTION IS REPLACED TO CONFORM TO THIS CODE.
 2. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH TO INDICATE THE AREAS TO RECEIVE NEW
 SILICONE COATING CLEARLY IDENTIFIED ON DRAWING; PROVIDE
 LENGTH & WIDTH OF AREAS NOT TO EXCEED 25% (9,220 SF) OF
 THE TOTAL SQUARE FOOTAGE(36,881) OF ROOF AREA.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  