Date |
Text |
2022-05-05 07:12:23 | 1ST REVIEW FBC-2020 RES. GAS |
| PERMIT- 22021171 |
| 5/5/2022 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. THE PERMIT APPLICATION |
| CALLS FOR A SEPARATE PERMIT FOR GAS HOWEVER A |
| SUB-PERMIT APPPICATION HAS NOW BEEN SUBMITTED. PLEASE |
| COMPLY WITH THE COMMENTS BELOW. |
| |
| 1) PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES |
| ALL NEW AND EXISTING GAS PIPING AND APPLIANCES AT THE |
| RESIDENCE- SECTION G2412.3 & G2412.4 FBC RES. REFER TO |
| FBC RES. CHAPTER 24 FUEL GAS- THE RISER SHALL INDICATE: |
| A) TYPE OF GAS- NATURAL OR LP. |
| B) DELIVERY PRESSURE AT THE METER. |
| C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| D) TYPES AND SIZES OF PIPING. |
| E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| TO THE MOST REMOTE APPLIANCE OUTLET. |
| F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE |
| UNIONS. |
| H) OUTLET PRESSURES AT REGULATORS. |
| I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| K) PIPE SIZING TABLES. |
| |
| 2) SUBMIT CUT SHEETS FOR ALL EQUIPMENT RELATING TO THE |
| GAS INSTALLATION SUCH AS REGULATORS, AND THE GENERATOR |
| FLEX CONNECTOR- SECTIONS G2421.2 & G2422.1.2 FBC RES. |
| PLEAE NOTE THE SUBMITTALS MAY BE DEFERRED AND BE ONSITE |
| FOR INSPECTION- SEC. 107.3.4.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |